Typical Field Wiring (Air Handler / Electrical Heat) - (Three Phase); Typical Field Wiring (Air Handler / Electrical Heat) (Single-Phase); Dehumidification Control - York THGD Series Installation Manual

R-410a outdoor split-system heat pump
Table of Contents

Advertisement

835961-UIM-D-0213
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
1
JUMPER TERMINALS E AND W TO HEAT
ON FIRST STAGE DURING EMERGENCY HEAT.
2
TERMINAL NOT USED ON ALL THERMOSTATS.
POWER WIRING
24V CONTROL WIRING
(NEC CLASS 2)
3
CHECK THE LOW VOLTAGE TERMINAL BLOCK ON THE INDOOR UNIT FOR THE ACTUAL ARRANGEMENT OF THE TERMINALS.
4
CONNECT POWER WIRING TO TERMINAL BLOCK 3TB ON UNITS WITHOUT ELECTRIC HEAT OR CIRCUIT BREAKER.
FIGURE 8: Typical Field Wiring (Air Handler / Electrical Heat) - (Three Phase)
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
R
B or C
Y
O
W
L or X
G
2
T
2
E
1
JUMPER TERMINALS E AND W TO HEAT
ON FIRST STAGE DURING EMERGENCY HEAT.
2
TERMINAL NOT USED ON ALL THERMOSTATS.
POWER WIRING
24V CONTROL WIRING
(NEC CLASS 2)
FIGURE 9: Typical Field Wiring (Air Handler / Electrical Heat) (Single-Phase)

DEHUMIDIFICATION CONTROL

A dehumidification control accessory 2HU06700124 may be used with
variable speed air handlers or furnaces in high humidity areas. This
control works with the variable speed indoor unit to provide cooling at a
reduced air flow, lowering evaporator temperature and increasing latent
capacity. The humidistat in this control opens the humidistat contacts on
humidity rise. To install, refer to instructions packaged with the acces-
sory. Prior to the installation of the dehumidification control, the jumper
across the HUMIDISTAT terminals on the indoor variable speed air han-
dler or furnace CFM selection board must be removed.
During cooling, if the relative humidity in the space is higher than the
desired set point of the dehumidification control, the variable speed
blower motor will operate at lower speed until the dehumidification con-
trol is satisfied. A 40-60% relative humidity level is recommended to
achieve optimum comfort.
8
THERMOSTAT
LOW VOLTAGE TERMINAL BLOCK
IN AIR HANDLER WITH ELECTRIC HEAT
R
B or C
Y
O
W
L or X
G
1
FIELD
2
T
INSTALLED
2
E
JUMPER
GND.
LUG
THERMOSTAT
LOW VOLTAGE TERMINAL BLOCK
IN AIR HANDLER WITH ELECTRIC HEAT
R
C
Y
O
W2
G
1
FIELD
W1
INSTALLED
JUMPER
BK
DEHUMIDIFICATION CONTROL CONNECTION
(Humidistat* Jumper must be removed)
GND.
LUG
CIRCUIT
BREAKER***
3
CHECK THE LOW VOLTAGE TERMINAL BLOCK ON THE INDOOR UNIT FOR THE ACTUAL ARRANGEMENT OF THE TERMINALS.
4
CONNECT POWER WIRING TO TERMINAL BLOCK 3TB ON UNITS WITHOUT ELECTRIC HEAT OR CIRCUIT BREAKER.
INDOOR UNIT
3,4
RED
R
BLK
B or C
YEL
Y
ORG
O
WHT
W2
PUR
BRN
G
W1
POWER
SUPPLY
208/230-3-60
460-3-60
INDOOR UNIT
3,4
RED
BLK
YEL
ORG
WHT
PUR
BRN
If a dehumidification control is installed, it is recommended that a mini-
mum air flow of 325 cfm/ton be supplied at all times.
For connection diagrams for all UPG equipment refer to "Low Voltage
System Wiring" document available online at www.upgnet.com in the
Product Catalog Section.
CFM SELECTION BOARD SETTINGS
For proper system operation the CFM Selection control jumpers must
be set properly.
Refer to the Tabular Data Sheet for the recommended air flow settings
for each size condensing unit.
Set the cooling speed per the instructions for the air handler or furnace
by selecting the correct COOL and ADJ taps. Verify the airflow using
the LED display on the CFM selection board.
OUTDOOR UNIT
DEFROST
CONTROL
CONTACTOR
R
C
T3
T2
T1
Y
M
O
L3
L2
L1
W
X
W1/66
POWER WIRING
208/230-3-60
460-3-60
OUTDOOR UNIT
DEFROST
CONTROL
R
CONTACTOR
C
T2
T1
Y
M
O
GND.
L2
L1
W
SCREW
X/L
W1/66
POWER WIRING
208/230-1-60
230-1-50
Johnson Controls Unitary Products
GND.
SCREW