Download Print this page

Garnet SPILLSTOP ULTRA 815-UHP/H User Manual page 9

Hydraulic version alarm controller with hose protection overfill prevention system

Advertisement

the S
float by at least two inches. Record this point as the shutdown
value. Ensure that the truck operator is aware of this value.
Ensure that this value and the empty reading are recorded
in the provided area in the operator's manual. The truck
operator must be given the owners manual upon delivery
with the data entered on the back of the manual.
6. Put the cover back on the S
proper operation by lifting the float. Verify the following
points:
a. The horn sounds and the pump stops at the horn alarm
b. Pressing the bypass button at this point silences the horn
c. The pump shuts down at the shut down alarm point.
d. At this point, pressing and holding the over-ride button
e. Raising the float any higher than the shut down point
f. Position the float below the shut down point but above
815UHP/H Manual
L
L float to the top of the tank, and then lower the
EE
EVE
point.
and restarts the pump.
sounds the horn and allows pump restart.
causes the pump to shut down regardless of whether the
button is pressed.
the horn alarm point, bypass the horn, and then verify
that the bypass is removed with the float at least one inch
above the bottom of the tank.
S
, and test the system for
PILL
TOP
Page 9