Endress+Hauser Proline 200 HART Brief Operating Instructions
Endress+Hauser Proline 200 HART Brief Operating Instructions

Endress+Hauser Proline 200 HART Brief Operating Instructions

Transmitter with vortex flow sensor

Advertisement

Quick Links

KA01326D/06/EN/01.18
71384790
Products
Brief Operating Instructions
Proline 200
HART
Transmitter with
Vortex flow sensor
These instructions are Brief Operating Instructions; they are
not a substitute for the Operating Instructions pertaining to
the device.
Transmitter Brief Operating Instructions
Contain information about the transmitter.
Sensor Brief Operating Instructions →  3
Solutions
Services

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Proline 200 HART and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Endress+Hauser Proline 200 HART

  • Page 1 Products Solutions Services KA01326D/06/EN/01.18 71384790 Brief Operating Instructions Proline 200 HART Transmitter with Vortex flow sensor These instructions are Brief Operating Instructions; they are not a substitute for the Operating Instructions pertaining to the device. Transmitter Brief Operating Instructions Contain information about the transmitter. Sensor Brief Operating Instructions →...
  • Page 2: Serial Number

    Proline 200 HART Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
  • Page 3 These Brief Operating Instructions are the Transmitter Brief Operating Instructions. The "Sensor Brief Operating Instructions" are available via: • Internet: www.endress.com/deviceviewer • Smart phone/tablet: Endress+Hauser Operations App Detailed information about the device can be found in the Operating Instructions and the other documentation: • Internet: www.endress.com/deviceviewer...
  • Page 4: Table Of Contents

    Table of contents Proline 200 HART Table of contents Document information ............5 Symbols used .
  • Page 5: Document Information

    Proline 200 HART Document information Document information Symbols used 1.1.1 Safety symbols Symbol Meaning DANGER! DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury. WARNING! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in WARNING serious or fatal injury.
  • Page 6 Document information Proline 200 HART Symbol Meaning Protective Earth (PE) A terminal which must be connected to ground prior to establishing any other connections. The ground terminals are situated inside and outside the device: • Inner ground terminal: Connects the protectiv earth to the mains supply.
  • Page 7: Basic Safety Instructions

    Proline 200 HART Basic safety instructions Basic safety instructions Requirements for the personnel The personnel must fulfill the following requirements for its tasks: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task. ‣ Are authorized by the plant owner/operator.
  • Page 8: Workplace Safety

    Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
  • Page 9: Device-Specific It Security

    Proline 200 HART Product description Device-specific IT security The device offers a range of specific functions to support protective measures on the operator' s side. These functions can be configured by the user and guarantee greater in-operation safety if used correctly.
  • Page 10: Wall Mounting

    Installation Proline 200 HART 4.2.1 Wall mounting 19 (0.6) 80 (3.15) A0033484  1 mm (in) 4.2.2 Post mounting 20 70 … ( 0.79 to 2.75) SW 13 A0033486  2 mm (in) Endress+Hauser...
  • Page 11: Turning The Transmitter Housing

    Proline 200 HART Installation Turning the transmitter housing To provide easier access to the connection compartment or display module, the transmitter housing can be turned. max. 350° 8 mm 8 mm A0032242 Release the fixing screw. Turn the housing to the desired position.
  • Page 12: Transmitter Post-Installation Check

    Installation Proline 200 HART With display module pulled out: Feed the cable into the gap between the housing and main electronics module and plug the display module into the electronics compartment until it engages. Reverse the removal procedure to reassemble the transmitter.
  • Page 13: Electrical Connection

    Proline 200 HART Electrical connection Electrical connection Connection conditions 5.1.1 Required tools • For cable entries: Use corresponding tools • For securing clamp: Allen key 3 mm • Wire stripper • When using stranded cables: Crimper for wire end ferrule •...
  • Page 14 Electrical connection Proline 200 HART 5.1.3 Connecting cable for remote version Connecting cable (standard) Standard cable 2 × 2 × 0.5 mm (22 AWG) PVC cable with common shield (2 pairs, pair-stranded) Flame resistance According to DIN EN 60332-1-2 Oil-resistance...
  • Page 15 Proline 200 HART Electrical connection Cable length 10 m (32 ft), 30 m (98 ft) Operating temperature When mounted in a fixed position: –50 to +105 °C (–58 to +221 °F); when cable can move freely: –25 to +105 °C (–13 to +221 °F) UV radiation may cause damage to the outer jacket of the cable.
  • Page 16: Terminal Assignment

    Electrical connection Proline 200 HART 5.1.4 Terminal assignment Transmitter 4-20 mA HART connection version with additional inputs and outputs – – – – – – A0033475 A0033475 Maximum number of terminals Maximum number of terminals for order code for Terminals 1 to 6: "Accessory mounted", option NA "Overvoltage...
  • Page 17 Proline 200 HART Electrical connection Connecting cable for remote version Transmitter and sensor connection housing In the case of the remote version, the sensor and transmitter are mounted separately from on another and connected by a connecting cable. Connection is performed via the sensor connection housing and the transmitter housing.
  • Page 18 Electrical connection Proline 200 HART Terminal number Assignment Cable color Connecting cable Supply voltage Brown Grounding White RS485 (+) Yellow RS485 (–) Green Connecting cable (option "mass pressure-/temperature-compensated") Order code for "Sensor version; DSC sensor; measuring tube", option DA, DB, DC, DD –...
  • Page 19 Proline 200 HART Electrical connection 5.1.5 Requirements for the supply unit Supply voltage Transmitter An external power supply is required for each output. Supply voltage for a compact version without a local display Order code for "Output" Minimum Maximum terminal voltage...
  • Page 20 Electrical connection Proline 200 HART • R ≤ (U ): 0.022 A term. min • R ≤ 500 Ω R [W] U [V] A0033472  5 Load for a compact version without local operation Operating range 1.1 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/ switch output"...
  • Page 21: Connecting The Measuring Device

    Proline 200 HART Electrical connection Remove dummy plug if present. If the measuring device is supplied without cable glands: Provide suitable cable gland for corresponding connecting cable. If the measuring device is supplied with cable glands: Observe requirements for connecting cables →  13.
  • Page 22 Electrical connection Proline 200 HART Push the cable through the cable entry . To ensure tight sealing, do not remove the sealing ring from the cable entry. Strip the cable and cable ends. In the case of stranded cables, also fit ferrules.
  • Page 23 Proline 200 HART Electrical connection The following procedure (in the action sequence given) is recommended for the remote version: Mount the sensor and transmitter. Connect the connecting cable for the remote version. Connect the transmitter. How the connecting cable is connected in the transmitter housing depends on the measuring device approval and the version of the connecting cable used.
  • Page 24 Electrical connection Proline 200 HART A0034171  6 Sample graphic Connecting cable (standard, reinforced) Guide the connecting cable through the cable entry and into the connection housing (if using a connecting cable without an M12 device plug, use the shorter stripped end of the connecting cable).
  • Page 25 Proline 200 HART Electrical connection Reverse the removal procedure to reassemble the connection housing. Connecting the transmitter Connecting transmitter via plug A0034172 ‣ Connect the plug. Connecting transmitter via terminals 3 mm A0034173 Loosen the securing clamp of the electronics compartment cover.
  • Page 26 Electrical connection Proline 200 HART TX 10 8 mm A0034174 Loosen the locking screw of the transmitter housing. Loosen the securing clamp of the transmitter housing. ~15° A0034175  7 Sample graphic Turn the transmitter housing to the right until it reaches the marking.
  • Page 27 Proline 200 HART Electrical connection A0034176  8 Sample graphic A0034177  9 Sample graphic Connecting cable (standard, reinforced) Disconnect the signal cable from the connection board of the wall housing . by pressing in the locking clip on the connector. Remove the transmitter housing.
  • Page 28: Ensuring The Degree Of Protection

    Electrical connection Proline 200 HART 11. Connect the cable shield via the cable strain relief. 12. Tighten the screws for the cable strain relief using a torque in the range of 1.2 to 1.7 Nm. 13. Reverse the removal procedure to reassemble the transmitter housing.
  • Page 29: Post-Connection Check

    Proline 200 HART Electrical connection To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following steps after the electrical connection: Check that the housing seals are clean and fitted correctly. Dry, clean or replace the seals if necessary.
  • Page 30: Operation Options

    Operation options Proline 200 HART Operation options Overview of operation options A0032226 Local operation via display module Computer with operating tool (e.g. FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM) Field Xpert SFX350 or SFX370 Field Communicator 475 Control system (e.g. PLC)
  • Page 31: Structure And Function Of The Operating Menu

    Proline 200 HART Operation options Structure and function of the operating menu 6.2.1 Structure of the operating menu Operating menu for operators and maintenances Language Operation task-oriented Setup Diagnostics Operating menu for experts Expert function-oriented A0014058-EN  10 Schematic structure of the operating menu 6.2.2...
  • Page 32: Access To The Operating Menu Via The Local Display

    Operation options Proline 200 HART Access to the operating menu via the local display X X X X X X 19.184 mA 12.5 X X X X X X Language 20.50 Ã English Deutsch Español Français Xxxxxxx A B C D E F G H I J K M N O P Q R S T U V W +0.000 Xx...
  • Page 33 Proline 200 HART Operation options 6.3.1 Operational display Explanatory symbols for the measured value Status area • Depends on the device version, e.g.: The following symbols appear in the status area of the – : Volume flow operational display at the top right: –...
  • Page 34: Operating Elements

    Operation options Proline 200 HART Numeric editor Confirms selection. Moves the input position one position to the left. Exits the input without applying the changes. Inserts decimal separator at the input position. Inserts minus sign at the input position. Clears all entered characters.
  • Page 35: Access To The Operating Menu Via The Operating Tool

    Proline 200 HART System integration Keys and meaning Reduces the contrast (brighter setting). Plus/Enter key combination (press and hold down the keys simultaneously) Increases the contrast (darker setting). Minus/Plus/Enter key combination (press the keys simultaneously) For operational display:Enables or disables the keypad lock.
  • Page 36: Switching On The Measuring Device

    Commissioning Proline 200 HART Switching on the measuring device ‣ After a successful function check, switch on the measuring device.  After a successful startup, the local display switches automatically from the startup display to the operational display. If nothing appears on the local display or a diagnostic message is displayed, refer to the Operating Instructions for the device →...
  • Page 37: Defining The Tag Name

    Proline 200 HART Commissioning The desired units can be selected in the System units submenu. The wizards systematically guide the user through all the parameters required for configuration, such as parameters for measurement or outputs. The wizards available in the particular device can vary on account of the device version (e.g.
  • Page 38: Protecting Settings From Unauthorized Access

    Commissioning Proline 200 HART Parameter overview with brief description Parameter Description User entry Factory setting Device tag Enter the name for the Max. 32 characters, such as Prowirl measuring point. letters, numbers or special characters (e.g. @, %, /). Protecting settings from unauthorized access...
  • Page 39 Proline 200 HART Commissioning Configuring the current output Configure current output. Configuring the external compensation With Wet Steam Detection/Measurement application package: In the Steam quality parameter, select the Calculated value option. For detailed information on the basic conditions for wet steam applications, see the Special Documentation.
  • Page 40 Commissioning Proline 200 HART 8.7.3 Gas applications For accurate mass or corrected volume measurement, it is recommended to use the pressure-/temperature-compensated sensor version. If this sensor version is not available, read in the pressure via the current input/HART. If neither of these two options is possible, the pressure can also be entered as a fixed value in the Fixed process pressure parameter.
  • Page 41 Proline 200 HART Commissioning Gas mixture Forming gas for steel mills and rolling mills, e. g. N Select medium Navigation: Setup → Medium selection Call up the Medium selection wizard. In the Select medium parameter, select the Gas option. In the Select gas type parameter, select the Gas mixture option.
  • Page 42 In the Reference temperature parameter enter the temperate for calculating the reference density. Endress+Hauser recommends the use of active pressure compensation. This fully rules out the risk of measured errors due to pressure variations and incorrect entries . Natural gas...
  • Page 43 12. In the Relative density parameter, enter the relative density of the natural gas. Endress+Hauser recommends the use of active pressure compensation. This fully rules out the risk of measured errors due to pressure variations and incorrect entries .
  • Page 44: Diagnostic Information

    Diagnostic information Proline 200 HART In the Reference density parameter, enter the reference density of the fluid. In the Reference pressure parameter, enter the reference pressure of the fluid. In the Reference temperature parameter, enter the fluid temperature associated with the reference density.
  • Page 45 Proline 200 HART Diagnostic information X X X X X X X X X X X X X X 20.50 S801 Supply voltage Menu Diagnostic list Diagnostics 1 S801 Supply voltage Diagnostics 2 Diagnostics 3 Supply voltage (ID:203) S801 0d00h02m25s...
  • Page 48 www.addresses.endress.com...

Table of Contents