Products Solutions Services KA01326D/06/EN/01.18 71384790 Brief Operating Instructions Proline 200 HART Transmitter with Vortex flow sensor These instructions are Brief Operating Instructions; they are not a substitute for the Operating Instructions pertaining to the device. Transmitter Brief Operating Instructions Contain information about the transmitter. Sensor Brief Operating Instructions →...
Proline 200 HART Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
Page 3
These Brief Operating Instructions are the Transmitter Brief Operating Instructions. The "Sensor Brief Operating Instructions" are available via: • Internet: www.endress.com/deviceviewer • Smart phone/tablet: Endress+Hauser Operations App Detailed information about the device can be found in the Operating Instructions and the other documentation: • Internet: www.endress.com/deviceviewer...
Proline 200 HART Document information Document information Symbols used 1.1.1 Safety symbols Symbol Meaning DANGER! DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury. WARNING! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in WARNING serious or fatal injury.
Page 6
Document information Proline 200 HART Symbol Meaning Protective Earth (PE) A terminal which must be connected to ground prior to establishing any other connections. The ground terminals are situated inside and outside the device: • Inner ground terminal: Connects the protectiv earth to the mains supply.
Proline 200 HART Basic safety instructions Basic safety instructions Requirements for the personnel The personnel must fulfill the following requirements for its tasks: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task. ‣ Are authorized by the plant owner/operator.
Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
Proline 200 HART Product description Device-specific IT security The device offers a range of specific functions to support protective measures on the operator' s side. These functions can be configured by the user and guarantee greater in-operation safety if used correctly.
Proline 200 HART Installation Turning the transmitter housing To provide easier access to the connection compartment or display module, the transmitter housing can be turned. max. 350° 8 mm 8 mm A0032242 Release the fixing screw. Turn the housing to the desired position.
Installation Proline 200 HART With display module pulled out: Feed the cable into the gap between the housing and main electronics module and plug the display module into the electronics compartment until it engages. Reverse the removal procedure to reassemble the transmitter.
Proline 200 HART Electrical connection Electrical connection Connection conditions 5.1.1 Required tools • For cable entries: Use corresponding tools • For securing clamp: Allen key 3 mm • Wire stripper • When using stranded cables: Crimper for wire end ferrule •...
Page 14
Electrical connection Proline 200 HART 5.1.3 Connecting cable for remote version Connecting cable (standard) Standard cable 2 × 2 × 0.5 mm (22 AWG) PVC cable with common shield (2 pairs, pair-stranded) Flame resistance According to DIN EN 60332-1-2 Oil-resistance...
Page 15
Proline 200 HART Electrical connection Cable length 10 m (32 ft), 30 m (98 ft) Operating temperature When mounted in a fixed position: –50 to +105 °C (–58 to +221 °F); when cable can move freely: –25 to +105 °C (–13 to +221 °F) UV radiation may cause damage to the outer jacket of the cable.
Electrical connection Proline 200 HART 5.1.4 Terminal assignment Transmitter 4-20 mA HART connection version with additional inputs and outputs – – – – – – A0033475 A0033475 Maximum number of terminals Maximum number of terminals for order code for Terminals 1 to 6: "Accessory mounted", option NA "Overvoltage...
Page 17
Proline 200 HART Electrical connection Connecting cable for remote version Transmitter and sensor connection housing In the case of the remote version, the sensor and transmitter are mounted separately from on another and connected by a connecting cable. Connection is performed via the sensor connection housing and the transmitter housing.
Page 18
Electrical connection Proline 200 HART Terminal number Assignment Cable color Connecting cable Supply voltage Brown Grounding White RS485 (+) Yellow RS485 (–) Green Connecting cable (option "mass pressure-/temperature-compensated") Order code for "Sensor version; DSC sensor; measuring tube", option DA, DB, DC, DD –...
Page 19
Proline 200 HART Electrical connection 5.1.5 Requirements for the supply unit Supply voltage Transmitter An external power supply is required for each output. Supply voltage for a compact version without a local display Order code for "Output" Minimum Maximum terminal voltage...
Page 20
Electrical connection Proline 200 HART • R ≤ (U ): 0.022 A term. min • R ≤ 500 Ω R [W] U [V] A0033472 5 Load for a compact version without local operation Operating range 1.1 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/ switch output"...
Proline 200 HART Electrical connection Remove dummy plug if present. If the measuring device is supplied without cable glands: Provide suitable cable gland for corresponding connecting cable. If the measuring device is supplied with cable glands: Observe requirements for connecting cables → 13.
Page 22
Electrical connection Proline 200 HART Push the cable through the cable entry . To ensure tight sealing, do not remove the sealing ring from the cable entry. Strip the cable and cable ends. In the case of stranded cables, also fit ferrules.
Page 23
Proline 200 HART Electrical connection The following procedure (in the action sequence given) is recommended for the remote version: Mount the sensor and transmitter. Connect the connecting cable for the remote version. Connect the transmitter. How the connecting cable is connected in the transmitter housing depends on the measuring device approval and the version of the connecting cable used.
Page 24
Electrical connection Proline 200 HART A0034171 6 Sample graphic Connecting cable (standard, reinforced) Guide the connecting cable through the cable entry and into the connection housing (if using a connecting cable without an M12 device plug, use the shorter stripped end of the connecting cable).
Page 25
Proline 200 HART Electrical connection Reverse the removal procedure to reassemble the connection housing. Connecting the transmitter Connecting transmitter via plug A0034172 ‣ Connect the plug. Connecting transmitter via terminals 3 mm A0034173 Loosen the securing clamp of the electronics compartment cover.
Page 26
Electrical connection Proline 200 HART TX 10 8 mm A0034174 Loosen the locking screw of the transmitter housing. Loosen the securing clamp of the transmitter housing. ~15° A0034175 7 Sample graphic Turn the transmitter housing to the right until it reaches the marking.
Page 27
Proline 200 HART Electrical connection A0034176 8 Sample graphic A0034177 9 Sample graphic Connecting cable (standard, reinforced) Disconnect the signal cable from the connection board of the wall housing . by pressing in the locking clip on the connector. Remove the transmitter housing.
Electrical connection Proline 200 HART 11. Connect the cable shield via the cable strain relief. 12. Tighten the screws for the cable strain relief using a torque in the range of 1.2 to 1.7 Nm. 13. Reverse the removal procedure to reassemble the transmitter housing.
Proline 200 HART Electrical connection To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following steps after the electrical connection: Check that the housing seals are clean and fitted correctly. Dry, clean or replace the seals if necessary.
Operation options Proline 200 HART Operation options Overview of operation options A0032226 Local operation via display module Computer with operating tool (e.g. FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM) Field Xpert SFX350 or SFX370 Field Communicator 475 Control system (e.g. PLC)
Proline 200 HART Operation options Structure and function of the operating menu 6.2.1 Structure of the operating menu Operating menu for operators and maintenances Language Operation task-oriented Setup Diagnostics Operating menu for experts Expert function-oriented A0014058-EN 10 Schematic structure of the operating menu 6.2.2...
Operation options Proline 200 HART Access to the operating menu via the local display X X X X X X 19.184 mA 12.5 X X X X X X Language 20.50 Ã English Deutsch Español Français Xxxxxxx A B C D E F G H I J K M N O P Q R S T U V W +0.000 Xx...
Page 33
Proline 200 HART Operation options 6.3.1 Operational display Explanatory symbols for the measured value Status area • Depends on the device version, e.g.: The following symbols appear in the status area of the – : Volume flow operational display at the top right: –...
Operation options Proline 200 HART Numeric editor Confirms selection. Moves the input position one position to the left. Exits the input without applying the changes. Inserts decimal separator at the input position. Inserts minus sign at the input position. Clears all entered characters.
Proline 200 HART System integration Keys and meaning Reduces the contrast (brighter setting). Plus/Enter key combination (press and hold down the keys simultaneously) Increases the contrast (darker setting). Minus/Plus/Enter key combination (press the keys simultaneously) For operational display:Enables or disables the keypad lock.
Commissioning Proline 200 HART Switching on the measuring device ‣ After a successful function check, switch on the measuring device. After a successful startup, the local display switches automatically from the startup display to the operational display. If nothing appears on the local display or a diagnostic message is displayed, refer to the Operating Instructions for the device →...
Proline 200 HART Commissioning The desired units can be selected in the System units submenu. The wizards systematically guide the user through all the parameters required for configuration, such as parameters for measurement or outputs. The wizards available in the particular device can vary on account of the device version (e.g.
Commissioning Proline 200 HART Parameter overview with brief description Parameter Description User entry Factory setting Device tag Enter the name for the Max. 32 characters, such as Prowirl measuring point. letters, numbers or special characters (e.g. @, %, /). Protecting settings from unauthorized access...
Page 39
Proline 200 HART Commissioning Configuring the current output Configure current output. Configuring the external compensation With Wet Steam Detection/Measurement application package: In the Steam quality parameter, select the Calculated value option. For detailed information on the basic conditions for wet steam applications, see the Special Documentation.
Page 40
Commissioning Proline 200 HART 8.7.3 Gas applications For accurate mass or corrected volume measurement, it is recommended to use the pressure-/temperature-compensated sensor version. If this sensor version is not available, read in the pressure via the current input/HART. If neither of these two options is possible, the pressure can also be entered as a fixed value in the Fixed process pressure parameter.
Page 41
Proline 200 HART Commissioning Gas mixture Forming gas for steel mills and rolling mills, e. g. N Select medium Navigation: Setup → Medium selection Call up the Medium selection wizard. In the Select medium parameter, select the Gas option. In the Select gas type parameter, select the Gas mixture option.
Page 42
In the Reference temperature parameter enter the temperate for calculating the reference density. Endress+Hauser recommends the use of active pressure compensation. This fully rules out the risk of measured errors due to pressure variations and incorrect entries . Natural gas...
Page 43
12. In the Relative density parameter, enter the relative density of the natural gas. Endress+Hauser recommends the use of active pressure compensation. This fully rules out the risk of measured errors due to pressure variations and incorrect entries .
Diagnostic information Proline 200 HART In the Reference density parameter, enter the reference density of the fluid. In the Reference pressure parameter, enter the reference pressure of the fluid. In the Reference temperature parameter, enter the fluid temperature associated with the reference density.
Page 45
Proline 200 HART Diagnostic information X X X X X X X X X X X X X X 20.50 S801 Supply voltage Menu Diagnostic list Diagnostics 1 S801 Supply voltage Diagnostics 2 Diagnostics 3 Supply voltage (ID:203) S801 0d00h02m25s...