Download Print this page

Dunkirk Q95M-200 Installation, Operation & Maintenance Manual page 8

Gas-fired direct vent modulating hot water boiler

Advertisement

6.2 Combustion
Air and Vent
Pipe Requirements
• This boiler requires dedicated direct vent system.
• In direct vent system all air for combustion is taken
directly from outside atmosphere,
and all fiue products
are discharged to outside atmosphere.
• Combustion air and vent pipe connections must
terminate
together in same atmospheric pressure
zone, either through roof or sidewall (roof termination
preferred).
See Figures 5 and 6 for required clearances.
For proper set up of concentric vent termination
see
Figure 7 and Figure 8.
Solvent
cements
are combustible.
Keep away from
heat, sparks,
and open flame.
Use only in well
ventilated
areas. Avoid breathing
in vapor or allowing
contact
with skin or eyes. Failure these instructions
could result in fire, personal
injury,
or death.
• Locate combustion air inlet as far away as possible
from swimming
pool and swimming
pool pump house.
• All combustion air and vent pipes must be airtight and
watertight.
Combustion air and vent piping must also
terminate
as shown in "Combustion
Air and Vent Pipe"
section.
• Vent connections serving appliances vented by
natural draft shall not be connected into any portion
of mechanical draft systems operating under positive
pressure.
• Covering non-metallic
vent pipe and fittings with
thermal insulation shall be prohibited.
6.3 Condensate
Drain
Requirements
• Condensate trap provided with boiler, an additional
trap is not required and should not be used.
• Pitch condensate drain line down to floor drain at
minimum
of 1/4"per foot. External condensate pump
(not furnished)
may be used if floor drain is not
available.
• Condensate pump must be designed for fiue gas
condensate application.
• Wood frame or blocks may be used to raise boiler
to maintain drain pitch or to be above external
condensate pump reservoir.
• If boiler is not level, condensate drain lines will not
function properly.
Adjustable feet are located on boiler
to make up for minor surface irregularities
or tilt.
• 115 volt AC receptacle provided on control panel to
provide power for external condensate pump if used.
6.4
Removal
of Existing
Boiler
From
Common
Vent
System
When an existing boiler is removed from a common
venting system, the common venting system is likely to be
too large for proper venting of the appliances remaining
connected to it. At the time of removal of an existing boiler,
the following steps shall be followed with each appliance
remaining connected to the common venting system
placed in operation,
while the other appliances remaining
connected to the common venting system are not in
operation.
1.
Seal any unused openings in the common venting
system.
2.
Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage, or
restrictions,
leakage, corrosion and other deficiencies
which could cause an unsafe condition.
3.
In-so-far
as is practical, close all building doors and
windows and all doors between the space in which the
appliances remaining connected to the common venting
system are located and other spaces of the building.
Turn on clothes dryer and any appliance not connected
to the common venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhaust, so
they will operate at maximum speed. Do not operate a
summer exhaust fan. Close fire dampers.
4.
Place in operation the appliance being inspected.
Follow the lighting instructions.
Adjust thermostat
so
appliances will operate continuously.
5.
Test for spillage at the draft hood relief opening after 5
minutes of main burner operation. Use the flame of a
match or candle, or the smoke from a cigarette, cigar
or pipe.
6.
After it has been determined
that each appliance
remaining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fire place dampers,
and any other gas-burning
appliance to their previous
condition of use.
7.
Any improper operation of the common venting system
should be corrected so the installation
conforms with
the National Fuel Code, NFPA-54/ANSI -Z223.1 and/or
the Natural Gas and Propane Installation
Code, CAN/
CSA B149.1. When re-sizing any portion of common
venting system, common venting system should be re-
sized to approach minimum
size as determined
using
appropriate
tables in Chapter 13 of the National Fuel
Gas Code, NFPA-54/ANSI- Z223.1 and/or the Natural
Gas and Propane Installation
Code, CAN/CSA B149.1.

Advertisement

loading