General Guidelines
When Using Antifreeze
Use only antifreeze
products
recommended
for use with
aluminum
boilers,
as listed
in
this addendum.
See Table
1, page 48.
Continuous
addition
of make-up
water
will dilute
power
of antifreeze
and change
buffers
ability
to
maintain
pH.
Flush old antifreeze
from system.
Flush boiler and
system
separately.
Do not use antifreeze
unless
required.
Antifreeze,
if needed,
must
be of type listed on
next page due to their
operational
characteristics
of : type 356 T6 aluminum
at operating
temperatures
between
20°F (-6.7°C)
and 250°F
(121°C).
(See Table 1 for allowable
products.)
Always
clean system
prior to using antifreeze
as
stated
in this supplement.
Be sure to follow
antifreeze
manufacturer's
instructions
for use, safe handling
and storage
of
their
products.
Refer to MSDS (Material
Safety
Data Sheets)
provided
by antifreeze
manufacturer
for potential
hazards
and first aid procedures
for
exposure
or ingestion.
Antifreeze
will raise pH of hydronic
solution
in
heating
system
above
recommended
level due to
corrosion
inhibitors.
Solution
must
be treated
to
maintain
a pH within
recommended
level. Follow
antifreeze
manufacturer's
instructions
to adjust
pH.
If system
has leaked,
water
and antifreeze
chemistry
will need to be adjusted.
To avoid
damage
to boiler, check
pH and chemistry
of boiler
solution
and consult
the antifreeze
manufacturer
for recommendations.
It is recommended
that
pH reading
be taken
annually,
and adjusted
as necessary.
Follow
antifreeze/inhibitor
manufacturer's
instructions
for
details
on how to adjust
pH.
Antifreeze
solutions
can break
down over time.
Failure to check antifreeze
chemistry
on annual
basis
may result
in accelerated
corrosion
of
boiler and other
system
components.
Consult
with
antifreeze
manufacturer
for recommendations.
Use of antifreeze
in any boiler will reduce
heating
capacity
as much as 10-20%.
Take
into consideration
when sizing
heating
system,
pumps and expansion
tank.
Consult
antifreeze
manufacturer's
literature
for specific
information
on reduced
capacity.
Using antifreeze
manufacturer's
instructions,
determine
freezing
temperature
needed
and use
correct
amount
of antifreeze.
Never exceed
50%
antifreeze
by volume.
Boiler operating
pressure
must
remain
below
15
psi for antifreeze
solutions
that specify
a maximum
of 250°F (121°C).
Otherwise,
increase
system
operating/tank
pressure
to 20 psig,
Note"
Refer
to expansion
tank
manufacturer
instructions
for
adjusting
tank
pressure.