WARNING: When you insert or remove the module while backplane power is
on, an electric arc can occur. This could cause an explosion in hazardous
location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electric arcing causes excessive wear to contacts on both the module
and its mating connector. Worn contacts may create electrical resistance that
can affect module operation.

European Hazardous Location Approval

The following modules are European Zone 2 approved: 1794-IC16, 1794-OC16.
The following applies to products marked
Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and
Safety Requirements relating to the design and construction of such equipment given in
Annex II to EU Directive 2014/34/EU. See the EU Declaration of Conformity at
http://www.rockwellautomation.com/global/certification/overview.page
The type of protection is II 3G Ex nA IIC T3 Gc according to EN 60079-15.
Comply to Standards EN 60079-0:2012, EN 60079-15:2010, reference certificate number
LCIE 01 ATEX 6020 X.
Are intended for use in areas in which explosive atmospheres caused by gases, vapors,
mists, or air are unlikely to occur, or are likely to occur only infrequently and for short
periods. Such locations correspond to Zone 2 classification according to ATEX directive
2014/34/EU.
FLEX I/O 48V DC Digital Input and Output Modules
Publication 1794-IN105C-EN-P - July 2018
II 3 G:
for details.