Installation and Maintenance Manual
E2K-402-0817 Rev. 3

Section 2: M2CP Electical Hook Up

Remove PWR and TBM covers to expose terminals for customer wiring. Bettis Modular
Control Package (M2CP) is available configured in many combinations of electrical and
electronic parts. Refer to WIRING DIAGRAM and Bettis JOB SPEC SHEET for components
provided by Bettis. Connect control wires to TBM and Power (motor) Voltage to PWR
terminals. If optional M2CP mounted circuit breaker was specified, connect power voltage
leads to circuit breaker. Bettis terminal blocks are furnished with wire binding screw
connectors with rising captive plates, allowing field connection by several methods: 1) strip
and connect bare wire, 2) strip and install wire ferrule, 3) strip and install crimp-on insulated
or non-insulated ring tongue or similar terminal. Circuit Breaker accepts 1) bare wire strip, or
2) wire ferrule.
Figure 2
PWR
Terminal s
bare wire strip
M2CP Electrical Hook Up
.375 10 AWG max
375 10 AW
A A G max
#8-32 (600V max)
#8-32 (600V max)
.400
Section 2: M2CP Electrical Hook Up
.315 12 AWG max
TBM
#6-32 (230V max)
Terminal s
.3
.315
bare w w i i r r e e
bare
bare wire strip
s s t t r r i i p p
Circuit
Breaker
bare wire strip
.450
18-8 AWG (600V max)
September 2018
4