Installation - Honeywell R7140G Installation Instructions Manual

Burner control modules
Table of Contents

Advertisement

Terminal
Typical Load
5 or 6
Ignition
Transformer/Pilot
Valve/First Stage Fuel Valve
7
Main Fuel Valve(s) (solenoid/
motorized/diaphragm) and
Vent Valve, if required
Device Initiate Standby Purge
R7140G 10 sec.
*
R7140L
R7140M
a
30 seconds with JR2 clipped and jumper from terminal 8 to terminal 15.
*
STANDBY and RUN can be an infinite time period.
** PURGE will be determined by which ST7800A purge card is selected; 15 timings are available from 2 seconds to 30 minutes.
NOTE: Allowable inrush can be up to ten times the pilot duty
rating.
EXAMPLE: Pilot duty rating = 50 VA.
At 120 V, running current is:
50/120 = 0.42A.
Maximum allowable inrush is ten times 0.42A = 4.2A.

INSTALLATION

When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and marked
on the product to make sure the product is suitable for
the application.
Table 4. Terminal Ratings.
4.5A ignition and 50 VA pilot duty, or
2.5A ignition and 75 VA pilot duty.
250 VA pilot duty or 65 VA pilot duty in parallel with motorized valve(s) using a total of
1150 VA locked rotor (inrush), 460 VA to open, and 250 VA to hold or motorized valve(s)
using a total of 1500 VA locked rotor (inrush), 600 VA to open, and 250 VA to hold.
Table 5. Sequence Timing for Normal Operation.
Flame
Establishing
Period
Pilot
Main
**
4 or 10
10, 15
sec.
a
sec.
or
intermittent.
10 or 15
a
sec.
10 sec. or
intermittent
R7140G,L,M BURNER CONTROL MODULES
Maximum Rating at 120 Vac, 60 Hz
Post
Purge
Run
Timing Interlock Circuits
*
15 sec. Pre-Ignition,
Running, Low Fire
Pre-Ignition,
Lockout High and
Low Fire
Pre-Ignition,
Running, isolated
Low Fire.
3. Installer must be a trained, experienced, flame
safeguard service technician.
4. After installation is complete, check out the product
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard.
Can cause property damage, severe injury,
or death.
To prevent possible hazardous burner operation, verify
safety requirements each time a control is installed on
a burner.
WARNING
Electrical Shock Hazard.
Can cause serious injury or death.
Disconnect the power supply before beginning
installation. More than one power supply disconnect
may be required.
5
Firing
Energy
Approval
Rate
Saving
Circuit
Pre-Purge
4-wire
No
UL/CSA
modulating
Modulating
FM/IRI
Modulating
2-wire
UL/CSA
isolated
On-Off.
On-Off-On
contacts
Code
Bodies
66-1153—2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R7140lR7140m

Table of Contents