R7140G,L,M BURNER CONTROL MODULES
Fig. 2. Mounting dimensions of R7140G,L,M Burner Control Module with Q520A Subbase, in in. (mm).
Terminal No.
G
Flame Sensor Earth Ground
Earth G
Earth Ground
L2(N)
Line Voltage Common
L1
Line Voltage Supply (L1)
3
Lockout/Running Interlock
4
Pre-Ignition Interlock Input
5
Pilot Valve/Ignition
6
Interrupted/Intermittent Pilot Valve/First Stage Oil Valve 120 Vac. See Table 4.
7
Main Fuel Valve
8
Burner Motor
9
Alarm
10
Firing Rate High Fire
11
Firing Rate Common
12
Firing Rate Modulate
13
Low Fire Switch Input
14
Firing Rate Low Fire
15
High Fire Switch Input
16
Burner Controller and Limits
17
Shutter
18
Ignition
F
Flame Sensor
a
The R7140 must have an earth ground providing a connection between the subbase and the control panel or the equipment. The earth
ground wire must be capable of conducting the current to blow the 15A fast blow fuse (or breaker) in the event of an internal short
circuit. The R7140 needs a low impedance ground connection to the equipment frame, which, in turn, needs a low impedance
connection to earth ground.
66-1153—2
(127)
1-1/4
(32)
5-3/4 (146)
Table 3. Terminal Ratings.
Description
a
a
BURNER CONTROL
5
POWER
PILOT
FLAME
MAIN
ALARM
RESET
S
5
(127)
7
(177)
120 Vac (+10/-15%), 50 or 60 Hz (±10%).
120 Vac, 8A run, 43A inrush.
120 Vac, 1 mA.
120 Vac. See Table 4.
120 Vac. See Table 4.
120 Vac, 9.8 AFL, 58.8 ALR (inrush).
120 Vac, 1A pilot duty.
120 Vac, 75 VA pilot duty.
120 Vac, 75 VA pilot duty.
120 Vac, 75 VA pilot duty.
120 Vac, 1 mA.
120 Vac, 75 VA pilot duty.
120 Vac, 1 mA.
120 Vac, 1 mA.
120 Vac, 0.5A.
120 Vac, 4.5A ignition.
60 to 220 Vac, current limited.
4
6-5/32
(156)
_
+
M22604
Ratings