Download Print this page

Siemens MJ-X Installation And Operation Manual page 72

Voltage regulator control panel
Hide thumbs Also See for MJ-X:

Advertisement

$SSHQGL[ * 0HQX 6WUXFWXUH 4XLFN 5HIHUHQFH
*
0HQX 6WUXFWXUH 4XLFN 5HIHUHQFH
*
1DYLJDWLQJ WKH 0HQX
Press to Cancel changes without saving.
Press to Reset displayed Max/Min item to
present value.
Press to Acknowledge displayed Alert.
Cancel
Change
Reset
Press to change settings.
(For configuration items only.)
*
)DVW3DWK .H\V
Fast-Path Keys
Volt Level
Press to view Forward Voltage setpoint. (Press again for Reverse)
Press to view Forward Bandwidth setpoint (Press again for Reverse)
Bandwidth
Press to view Forward Time Delay setpoint (Press again for Reverse)
Time Delay
Press to view Forward Line Drop Compensation (LDC) Resistance setpoint. (Press again for Reverse)
Resistance
+/ -
Press Change, then press here to change sign after viewing Resistance or Reactance Compensation.
Press to view Forward Line Drop Compensation (LDC) Reactance setpoint. (Press again for Reverse)
Reactance
Press to view First Active Alert. Repeat to scroll through Active Alerts.
Alert Select
VRC Select
Press to view Voltage Reduction Control (VRC) Status. Repeat to scroll through VRC settings.
VLC Select
Press to view Voltage Limit Control (VLC) Enable status. Repeat to scroll through VLC settings.
Op Counter
Press to view Total Operations Count. Repeat to scroll through <COUNTERS> items.
Voltage Test/
Press to view Voltage Calibration.
Calibration
[Set U2/P2 Switch (on right side) to U2 position to view "U2 Cal". Set U2/P2 Switch to P2 position to view "P2 Cal"].

Press once to reach menu heading.
Press twice to reach "home" (<METER>).
Press to scroll (left) across menu headings.
(From Meter to Passwords to Diagnostics, etc.)
Press Change, and then press here to move
cursor to the left.
Press to save changed settings.
Max
Save
Min
Function
Press to scroll (up) through data items
within column. Press Change, and then
press here to change setting choices.
Press to scroll (right) across menu headings.
(From Meter to Fw Demand to Rev Demand, etc.)
Menu
Press Change, and then press here to move
cursor to the right.
Press to scroll (down) through data items
within column. Press Change, and then
press here to change setting choices.
Press once to view Maximum.
Press again to view Minimum.
Press 3rd time to exit Max/min view.
6LHPHQV 3RZHU 7UDQVPLVVLRQ
'LVWULEXWLRQ //&

Advertisement