Replacing A Slicestor 2210 Power Supply Unit - IBM Cloud Object Storage System Hardware Maintenance Manual

Table of Contents

Advertisement

About this task
Do the following procedure to replace a power supply unit in Slicestor 1440 and 2440 systems. The
power supply is hot pluggable; therefore, the system does not need to be powered down.
Figure 1. Slicestor 1440 and 2440 - Front Panel
Procedure
1. Identify the power supply unit (PSU) that needs to be replaced.
Figure 2. Slicestor 1440 and 2440 - Layout
2. Disconnect the power supply unit's power cable.
3. Loosen the thumbnail screw on the removal clip.
4. Pinch the clip at the end of the power supply at the rear of the system and slide the power cable out.
5. Insert the new power supply until it clicks into place.
6. Reconnect the power supply unit's power cable.
7. Contact your Customer Success Engineer to verify that the system is functioning correctly.