5.3 Mains connection for DC motors
Caution
The maximum permissible deviation of the mains voltage from the voltage stated on the rating plate of the
motor is 10%.
The wiring diagram is supplied upon request.
1.
Remove the cover from the terminal block of the electric motor;
2.
Insert the cable through the cable gland;
3.
Connect the green/yellow lead to the PE terminal (earth);
4.
Connect the 24 VDC lead to terminal A1 and neutral lead to terminal A2;
5.
Using a hex bit, move the motor gearbox to a position between the two limit switches;
6.
Check the direction of rotation of the output shaft in relation to the limit switch and the control cabinet; if
necessary swap the leads on A1 and A2;
7.
Fit the terminal block cover and gasket back on the motor and tighten the cable gland;
8.
Make sure that the cables are clear of any moving parts.
5.4 Connecting the limit switch
Attention! Observe the maximum (peak) switching current rating of 6 A at 250 VAC.
The optional Goldline limit switches from De Gier, which have gold-plated contacts, must be used if the
control voltage is less than 30 V or the control current is less than 400 mA.
1.
Remove the black plastic protective cover from the motor gearbox;
2.
Insert the cable through the cable gland;
3.
Connect the working and emergency switches as indicated in the diagram below;
4.
Fit a jumper between contacts 1 and 7;
5.
Fit a jumper between contacts 6 and 10;
6.
Make sure that the cables are free and tighten the cable gland;
7.
Re-fit the black plastic protective cover on the motor gearbox.
Wiring diagram for working and emergency switches
De Gier B.V., Westlandseweg 9, 2291 PG WATERINGEN, THE NETHERLANDS, Tel. +31 (0)174 292089, Fax +31 (0)174 295644, E-mail: sales@degier.nl
INSTALLATION MANUAL
Electrical Connection
www.degier.eu
Version 1 – 2014 / 06 / 11
17