Module Data, Status, and Channel Configuration
Table 3.10 Effective Resolution and Range for 50-60 Hz Filter Frequency
Input
Raw/Proportional Data
Type
Over Full Input Range
Resolution
°C
°F
100Ω
0.224°C /
0.404°F/
Pt 385
14 counts
14 counts
200Ω
0.112°C /
0.202°F/
Pt 385
7 counts
7 counts
500Ω
0.176°C /
0.317°F/
Pt 385
11 counts
11 counts
1000Ω
0.352°C /
0.634°F/
Pt 385
22 counts
22 counts
100Ω
0.114°C /
0.205°F/
Pt
9 counts
9 counts
3916
200Ω
0.063°C /
0.114°F/
Pt
5 counts
5 counts
3916
500Ω
0.101°C /
0.182°F/
Pt
8 counts
8 counts
3916
1000Ω
0.101°C /
0.182°F/
Pt
8 counts
8 counts
3916
10Ω
15.381°C
27.686°F/
Cu 426
/ 2800
2800
counts
counts
120Ω
0.055°C /
0.099°F/
Ni 618
10 counts
10 counts
120Ω
0.042°C /
0.075°F/
Ni 672
8 counts
8 counts
604Ω
0.121°C /
0.181°F/
NiFe
22 counts
22 counts
518
150Ω
0.153Ω /67 counts
500Ω
0.046Ω /6 counts
1000Ω
0.092Ω /6 counts
3000Ω
0.641Ω /14 counts
Publication 1762-UM003A-EN-P - February 2003
Engineering Units x 1
Engineering Units x 10
Over Full Range
Over Full Range
Resolution
°C
°F
-2000
0.3°C /
0.540°F/
-200
to
3 counts
3 counts
to
+8500
+850
-2000
0.2°C /
0.360°F/
-200
to
2 counts
2 counts
to
+8500
+850
-2000
0.2°C /
0.360°F/
-200
to
2 counts
2 counts
to
+8500
+850
-2000
0.4°C /
0.720°F/
-200
to
4 counts
4 counts
to
+8500
+850
-2000
0.2°C /
0.360°F/
-200
to
2 counts
2 counts
to
+6300
+630
-2000
0.1°C /
0.18° C /
-200
to
1 count
1 count
to
+6300
+630
-2000
0.1°C /
0.18°F /
-200
to
1 counts
1 counts
to
+6300
+630
-2000
0.1°C /
0.18°F /
-200
to
1 count
1 count
to
+6300
+630
-1000
15.40°C /
27.720°F/
-100
to
154
154
to
+2600
counts
counts
+260
-1000
0.1°C /
0.18°F /
-100
to
1 count
1 count
to
+2600
+260
-800 to
0.1°C /
0.18°F /
-80 to
+2600
1 count
1 count
+260
-1000
0.12°C /
0.18°F /
-100
to
1 count
1 count
to
+2000
+200
0 to
0.160Ω / 16 counts
0 to
+15000
+1500
0 to
0.1Ω / 1 count
0 to
+5000
+500
0 to
0.1Ω / 1 count
0 to
+10000
+1000
0 to
0.700Ω / 7 counts
0 to
+30000
+3000
Scaled for PID Over Full
Range
Resolution
°C
°F
°C
1.0°C/
1.8°F/
0.256°C/4
1 count
1 count
counts
1.0°C/
1.8°F/
0.128°C/
1 count
1 count
2 counts
1.0°C/
1.8°F/
0.192°C/
1 count
1 count
3 counts
1.0°C/
1.8°F/
0.385°C/
1 count
1 count
6 counts
1.0°C/
1.8°F/
0.152°C/
1 count
1 count
3 counts
1.0°C/
1.8°F/
0.101°C/
1 count
1 count
2 counts
1.0°C/
1.8°F/
0.101°C/
1 count
1 count
2 counts
1.0°C/
1.8°F/
0.101°C/
1 count
1 count
2 counts
16.00°C/
28.80°F/
15.381°C
16 counts
16 counts
/700
counts
1.0°C/
1.8°F/
0.066°C/
1 count
1 count
3 counts
1.0°C/
1.8°F/
0.042°C/
1 count
1 count
2 counts
1.2°C/
1.8°F/
0.132°C/
1 counts
1 count
6 counts
0.2Ω /2 counts
0.156Ω / 17 counts
1.0Ω / 1 count
0.061Ω / 2 count
1.0Ω / 1 count
0.122Ω / 2 counts
1.0Ω /1 count
0.732Ω /4 counts
Percent of Full Scale
0 to 100%
Resolution
Resolution
°F
°C
0.461°F/
0.315°C/
4 counts
3 counts
0.231°F/
0.210°C/
2 counts
2 counts
0.346°F/
0.210°C/
3 counts
2 counts
0.692°F/
0.420°C/
6 counts
4 counts
0.274°F/
0.166°C/
3 counts
2 counts
0.182°F/
0.083°C/
2 counts
1 count
0.182°F/
0.166°C/
2 counts
2 counts
0.182°F/
0.166°C/
2 counts
2 counts
27.686°F/
15.406°C/
700
428
counts
counts
0.119°F/
0.072°C/
3 counts
2 counts
0.075°F/
0.068°C/
2 counts
2 counts
0.198°F/
0.144°C/
6 counts
4 counts
0.165Ω / 11 counts
0.050Ω / 1 count
0.100Ω / 1 count
0.900Ω / 3 counts
°F
0.567°F/
3 counts
0.378°F/
2 counts
0.378°F/
2 counts
0.756°F/
4 counts
0.299°F/
2 counts
0.149°F/
1 count
0.299°F/
2 counts
0.299°F/
2 counts
27.732°F/
428
counts
0.130°F/
2 counts
0.122°F/
2 counts
0.216°F/
4 counts