Controls - Daikin VHF Installation And Maintenance Manual

Vertical stack water source heat pumps
Table of Contents

Advertisement

Table 12: MicroTech III unit controller terminals &
descriptions
H1 – 1
24
24 VAC Power Input
H1 – 2
C
24 VAC common
H2 – 1
SL1
Fan Main Required Output – Switched L1
H2 – 2
Blank Terminal
H2 – 3
N
Fan Main Required Output – Neutral
H3 – 1 HP1-1 Comp High Pressure Switch (HP1) Input Terminal 1
H3 – 2 HP1-2 Comp High Pressure Switch (HP1) Input Terminal 2
H4 – 1
1
Discharge Air Temp Sensor – Common
H4 – 2
Discharge Air Temp Sensor – Signal
H4 – 3
Leaving Water Temp Sensor – Common
H4 – 4
Leaving Water Temp Sensor – Signal
H5 – 1
1
H5 – 2
H5 – 3
H5 – 4
H5 – 5
H5 – 6
Connections to I/O Expansion Board
H5 – 7
H5 – 8
H5 – 9
H5 – 10
H5 – 11
H5 – 12
H6 – 1
1
Condensate Overflow Signal Input
H6 – 2
Compressor Suction Temp Sensor (LT1) – Common
H6 – 3
Compressor Suction Temp Sensor (LT1) – Signal
H6 – 4
Compressor Low Pressure Switch (LP1) – Source Voltage
H6 – 5
Compressor Low Pressure Switch (LP1) – Signal
H6 – 6
Reversing Valve – Common
H6 – 7
Reversing Valve – Output
H7 – 1
1
No Connection
H7 – 2
No Connection
H7 – 3
Red LED Output
H7 – 4
Green LED Output
H7 – 5
Yellow LED Output
H7 – 6
Red-Green-Yellow LED Common
H8 – 1
1
Isolation Valve/Pump Request Relay N/O
H8 – 2
Isolation Valve/Pump Request Relay N/C
H8 – 3
24 VAC Common
H9 – 1
1
Room Temp Sensor & Tenant Override – Signal
H9 – 2
Room Temp Sensor & Tenant Override – Common
TB1 – 1
1
Room Sensor – Status LED Output
TB1 – 2
2
Room Sensor – Fan Mode & Unit Mode Switches
TB1 – 3
3
Room Sensor – Setpoint Adjust Potentiometer
TB1 – 4
4
Room Sensor – Room Temp Sensor & Tenant Override
TB1 – 5
5
Room Sensor – DC Signal Common
TB2 – 1
R
24 VAC
TB2 – 2
A
Thermostat – Alarm Output
TB2 – 3
W2
Thermostat – Heat Stage #2 (W2) Input
TB2 – 4
W1
Thermostat – Heat Stage #1 (W1) Input
TB2 – 5
Y2
Thermostat – Cool Stage #2 (Y2) Input
TB2 – 6
Y1
Thermostat – Cool Stage #1 (Y1) Input
TB2 – 7
G
Thermostat – Fan Input
www.DaikinApplied.com
TB2 – 8
O
Thermostat – Heat Stage #3 (W3) Input
TB2 – 9
C
24 VAC Common
TB3 – 1
E
Emergency Shutdown Input
TB3 – 2
U
Unoccupied Input
L1 – 1
L1 - 1
Line Voltage Terminal 1
L1 – 2
L1 - 2
Line Voltage Terminal 2
L1 – 3
L1 - 3
Line Voltage Terminal 3
N1
N1
Neutral Terminal 1
N2
N2
Neutral Terminal 2
N3
N3
Neutral Terminal 3
Table 13: I/O expansion module connectors/terminals
H1 – 1
1
H1 – 2
H1 – 3
H1 – 4
H1 – 5
H1 – 6
Connections to Main Board
H1 – 7
H1 – 8
H1 – 9
H1 – 10
H1 – 11
H1 – 12
H2 – 1
1
Auxiliary Heat Stage #2 Output – N/O
H2 – 2
No Connection
H2 – 3
24 VAC Common
H3 – 1
1
Ext. 24 VAC In
H3 – 2
Ext. 24 VAC Common In
H3 – 3
HGR / Waterside Economizer Output – N/O
H3 – 4
Ext. 24 VAC Common
H3 – 5
EC Fan Motor Variable Speed Signal Output
H3 – 6
EC Fan Motor Variable Speed Signal – Common
H4 – 1
1
Entering Water Temp Sensor – Signal
H4 – 2
Entering Water Temp Sensor – Common
H5 – 1
1
No Connection
H5 – 2
No Connection
H5 – 3
Red LED Output
H5 – 4
Green LED Output
H5 – 5
Yellow LED Output
H5 – 6
Red-Green-Yellow LED Common
H6 – 1 HP2-1 Comp High Capacity High Press Sw (HP2) Input Terminal 1
H6 – 2 HP2-2 Comp High Capacity High Press Sw (HP2) Input Terminal 2
H7 – 1
Fan Speed Table Row Select – Signal
H7 – 2
Fan Speed Table Row Select – Common
H7 – 3
Thermostat – Heat Stage #4 (W4) Input – Signal
H7 – 4
Auxiliary 24 VAC Out
H8 – 1
1
Compressor – High Capacity Output – N/O
H8 – 2
24 VAC Common
H8 – 3
No Connection
H8 – 4
Auxiliary Heat Stage #1 / Hydronic Heat Output N/O (24 VAC)
H8 – 5
24 VAC Common
TB1 – 1
1
Humidistat Signal Input
TB1 – 2
2
Thermostat - Heat Stage #4 (W4) Input – Signal
38
C
ontrols
Vertical Stack WSHP • IM 986-11