10.4 Thyristor unit Configuration

Parameter
Password
Delay trigger
% HB
Firing type
Soft start time
N° burst
Delay time HB
Max power for SSR Input
Cycle time
N° of half period for Delayed triggering
10.4.1 Password
Operations: Write
Meaning:
If properly setted give the access to configuration
10.4.2 Delay triggering
Operations: Read/Write
Meaning:
It's correspond to a value in points (0-50, 0-32 Hex)
Each step is 0,1msec. Range is 0-5msec.
This parameter is the delay of firig in first half period with respect zero voltage crossing.
10.4.3 % HB
Operations: Read/Write
Meaning:
It's correspond to a value in point (0-255, 0-ff Hex)
This parameter is the value in % that decrease the load current to establish the HB current set
point
Example:
Load current
Parameter 124H
Parameter 2 will be setted at 8A
CD3000M-3PH up to 90A
N.
Notes
123
Write
124L
Read /write
124H
Read /write
125L
Read /write
125H
Read /write
126L
Read /write
126H
Read /write
127L
Read /write
127H
Read /write
128L
Read /write (Mantenere a 1)
128H
Read /write
= 10A
= 20%
51 Dec
47
Parameter 124H
33 Hex
Honeywell
Parameter 123
Parameter 124L