Installation Recommendations - Carrier 38YMA Installation And Start-Up Instructions Manual

Heat pump outdoor section

Advertisement

AIR IN
AIR DISCHARGE
AIR IN
AIR DISCHARGE
AIR IN
AIR DISCHARGE
NOTES:
1. ALLOW 30" CLEARANCE TO SERVICE END OF
UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12"
ON REMAINING SIDE, AND 24" BETWEEN
UNITS FOR PROPER AIRFLOW.
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE IS
55° F (UNLESS LOW AMBIENT CONTROL IS USED) MAX. 125° F.
UNIT
SIZE
018—048
1. Install suction tube adapter.
2. Install liquid flare-to-sweat adapter.
3. Install TXV on liquid flare-to-sweat adapter.
4. Connect external equalizer tube to fitting on suction tube
adapter.
5. Position sensing bulb on horizontal portion of suction tube
adapter. Secure using supplied hardware. Insulate bulb after
installation.
6. Leak check all connections.
DO NOT BURY MORE THAN 36 IN. OF REFRIGERANT
TUBING IN GROUND. If any section of tubing is buried,
there must be a 6-in. vertical rise to the valve connections on
the outdoor unit. If more than the recommended length is
buried, refrigerant may migrate to cooler buried section
during extended periods of unit shutdown, causing refrigerant
slugging and possible compressor damage at start-up.
Step 5—Make Piping Connections
Outdoor units may be connected to indoor sections using accessory
tubing package or field-supplied refrigerant grade tubing of correct
B
3 /8 " DIA TIEDOWN KNOCKOUTS
FIELD POWER
SUPPLY CONNECTION
FIELD CONTROL
SUPPLY CONNECTION
VAPOR
CONNECTION
LIQUID
CONNECTION
3. MAXIMUM OUTDOOR OPERATING AMBIENT IN HEATING MODE IS 66° F.
4. SERIES DESIGNATION IS THE 13TH POSITION OF THE UNIT
A
In.
34-15/16
Fig. 2 —Unit Reference Drawing
2
A
8
(2) PLACES
UNIT RATING
PLATE
ACCESS
PANEL
MODEL NUMBER.
B
C
In.
In.
30
4
size and condition. For tubing requirements beyond 50 ft, consult
Long-Line Application Guideline which is available at your local
distributor.
NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.

INSTALLATION RECOMMENDATIONS

1. Locate the unit away from windows.
2. Ensure that vapor and liquid line diameters are appropriate to
the capacity of the unit. (See Table 1.)
3. Run refrigerant tubes as directly as possible by avoiding
unnecessary turns and bends.
4. Leave some slack between the structure and the unit to absorb
vibration.
5. When passing refrigerant tubes through the wall, seal the
opening with RTV or other pliable silicon-based caulk. (See
Fig. 3.)
6. Avoid direct lineset contact with water pipes, ductwork, floor
joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with a
rigid wire or strap which comes in direct contact with the
tubing. (See Fig. 3.)
C
C L
D
SERIAL
PROD
MODEL
"
PISTON
ID
OD
3
/
16
FACTORY CHARGED R-22
LBS
POWER SUPPLY
PH
PERMISSIBLE VOLTAGE AT UNIT
MAX
SUITABLE FOR OUTDOOR USE
COMPRESSOR
VOLTS AC
PH
HZ
RLA
LRA
FAN MOTOR
VOLTS AC
PH
HZ
FLA
DESIGN/TEST PRESSURE GAGE
HI
PSI
kPa
LO
PSI
kPa
MINIMUM CIRCUIT AMPS
MAX OVERCURRENT PROTECTIVE DEVICE
TYPE
USA
MAX FUSE
MAX HACR CKT-BKR
MAX CKT-BKR
N/A
®
®
CARRIER CORP
INDIANAPOLIS IN
313948-401
REV A
D
In.
9-3/4
Kg
VOLTS
HZ
MIN
CANADA
N/A
46206
A92022