Measuring Ranges - Siemens 6ES7134-4FB51-0AB0 Manual

Distributed i/o 2ai u hs analog electronic module
Table of Contents

Advertisement

Analog value representation

4.3 Measuring ranges

Output value
The following table shows the representation of the binary analog values and the
corresponding decimal and hexadecimal representation of the units of the analog values.
The table below shows the resolutions 11, 12, 13, and 15 bit + sign. Each analog value is
entered left aligned in the ACCU. The bits marked with "x" are set to "0".
Table 4-2
Output values (SIMATIC S7 format)
Resolution in bits
11+S
12+S
13+S
15 + sign
4.3
Measuring ranges
Introduction
The following tables contain the digitized analog values for the measuring ranges of the
analog input modules.
Since the binary representation of the analog values is always the same, these tables
contain only a comparison of the measuring ranges with the units.
measuring ranges for voltage ± 2.5 V, ± 5 V and ± 10 V
Table 4-3
SIMATIC S7 format: measuring ranges ± 2.5 V, ± 5 V and ± 10 V
Measuring range
Measuring range
± 2.5 V
> 2,9397
2,9397
:
2,5001
2,5
1,86
:
-1,86
-2,50
-2,5001
:
-2,9397
< -2,9397
16
Units
Decimal
Hexadecimal
16
10
8
8
H
4
4
H
1
1
H
Measuring range
± 5 V
± 10 V
> 5,8794
> 11,7589
5,8794
11,7589
:
5,0002
10,0004
5,00
10,00
3,75
7,50
:
-3,75
-7,50
-5,00
-10,00
-5,0002
-10,0004
:
-5,8796
-11,759
< -5,8796
< -11,759
High byte
S 0 0 0 0 0 0 0
H
S 0 0 0 0 0 0 0
S 0 0 0 0 0 0 0
S 0 0 0 0 0 0 0
Decimal
32767
32511
:
:
27649
27648
20736
:
:
-20736
-27648
-27649
:
:
-32512
-32768
2AI U HS analog electronic module (6ES7134-4FB51-0AB0)
Analog value
Low byte
0 0 1 x x x x
0 0 0 1 x x x
0 0 0 0 1 x x
0 0 0 0 0 0 1
Units
Hexadecimal
7FFF
Overflow
H
7EFF
H
:
Overshoot range
6C01
H
6C00
H
5100
H
:
Rated range
AF00
H
9400
H
93FF
H
:
Undershoot range
8100
H
8000
Underflow
H
Manual, 04/2007, A5E01076015-01
Range

Hide quick links: