Ao (Analog Output) Setup - Quatrosense Environmental QEL Installation, Operation And Maintenance Manual

Q-controller monitor and control system
Table of Contents

Advertisement

AO (Analog Output) Setup

5.3.11
Click AO-Box list item will enter below configuration screen.
AO-Box
Enable/Disable
Description
Convert Mode
Reading at 4mA
Reading at 20mA
Assigned Input
Q-Controller System Operation Manual
86550-001-000 Rev B
Q-Controller only monitor and control enabled devices
Description for this channel of AO-Box
• Average Mode
• Peak Mode
Analog outputs may work with sensors and analog inputs. It's
allowed to assign more than one input per output channel. The
inputs could be averaged or taken the peak among the inputs as
the value to convert output current.
Assign a concentration for both the 4.0 milliamp signal, and the
20 milliamp signal. You may assign a larger concentration for 4.0
milliamps than for 20 milliamps; the Q-Controller will still
stretch a straight line signal between the two points.
See above
Define which inputs assigned to the AO channel
- 39 -