Monitoring Mode:
Simulation Mode:
Calibration Mode:
. Click Q-Controller icon to configure the Q-Controller communication settings
Scheduler #
Device Name:
Q-Controller System Operation Manual
86550-001-000 Rev B
Set the Q-Controller to read all connected inputs and control
outputs in real time
Simulation is to assist in testing the installation before
commissioning. When the simulation mode is selected, the Q-
Controller will stop polling remote input devices, you can
manually input simulation gas value or switch input status in tab
[Monitoring] screen. The Q-Controller will display the simulating
value and use it to calculate the statuses of relays and buzzer, as
well as 4-20mA analog output. This feature is able to evaluate the
user settings and testing the installation (e.g.: the travel of the
valve, fan speed, relay set points, etc. can be verified.)
This function is for calibration, system testing etc. When the
calibration mode is selected, the relay, buzzer and analog output,
etc., statuses will freeze in whatever state they are already in.
How many Schedulers in the Q-Controller System
The name will be used to display for this Q-Controller. It's also
used to be model name in Device Object in BACnet /IP protocol