LG PPWRDB000 Installation And Owner's Manual page 22

Hide thumbs Also See for PPWRDB000:
Table of Contents

Advertisement

SETTING AND USING METHOD
22
Setting functions (EHP products)
• Connection type setting: Setting based on system configuration
- In case of power indicator single composition: MASTER
- In case of central controller interface: SLAVE
※In 1.4 or higher version, SLAVE-RC setting is possible, and in case of central controller inter-
face, if one unit of SLAVE is set as SLAVE-RC, protection logic for distribution error by cen-
tral controller failure is operated.
C O N N E C T I O N :
S T A N D B Y
P : A U T O
W H M 1 : N O T U S E
W H M 2 : N O T U S E
' When the CONNECTION item flashes, press the SELECT button to enter the setting window.
Press the SELECT button at the item to set to save the setting and return to the initial setting
screen.
!
CAUTION
• When you set the connection type, you need to set only one unit as SLAVE RC Type.
• Standby power distribution method setting
Standby power: Power consumed by outdoor unit when all indoor units are turned off
- AUTO: Automatically distributes the standby power to all connected indoor units
- MANUAL: Does not distribute the standby power and saves separately
C O N N E C T I O N :
S T A N D B Y
P : A U T O
W H M 1 : N O T U S E
W H M 2 : N O T U S E
' When the STANDBY P item flashes, press the SELECT button to enter the setting window.
Press the SELECT button at the item to set to save the setting and return to the initial setting
window.
M A S T E R
M A S T E R
C O N N E C T I O N
T Y P E
1 . M A S T E R
2 . S L A V E
3 . S L A V E - R C
S T A N D B Y P O W E R
1 . A U T O
2 . M A N U A L