Cd30
IIn-Range Tolerance
Cd31
Stagger Start Offset Time
(Seconds)
Cd32
Current Limit (Amperes)
Cd33
Humidity Setpoint
Cd34
Economy Mode (On-Off)
Table 4–3 Controller Function Codes (Continued)
DESCRIPTION
The in-range tolerance will determine the temperature band around
the set point which will be designated as in-range. For normal tem-
perature control, control temperature is considered in range if it is with-
in setpoint in-range Tolerance. There are four possible values:
1 = +/- 0.5°C (+/-0.9°F)
2 = +/- 1.0°C (+/-1.8°°F)
3 = +/- 1.5°C (+/-2.7°F)
4 = +/- 2.0°C (+/-3.6°F) - Factory Default
If the control temperature is in-range, the green IN-RANGE light will be
illuminated.
In-range tolerance shall be set to +/- 2.0°C upon activation of dehumid-
ification or bulb mode (Cd33, Cd35, Cd48).
When CCPC is actively controlling, in-range tolerance is not consid-
ered.
"-----" will be displayed whenever Dehumidification or Bulb mode is en-
abled or when CCPC with six hour re-activation is actively controlling.
"-----" will be displayed whenever Frozen Economy Mode is operating.
The stagger start offset time is the amount of time that the unit will de-
lay at start-up, thus allowing multiple units to stagger their control initi-
ation when all units are powered up together. The eight possible offset
values are 0 (Factory Default), 3, 6, 9, 12, 15, 18 or 21 seconds.
The current limit is the maximum current draw allowed on any phase
at any time. Limiting the unit's current reduces the load on the main
power supply. When desirable, the limit can be lowered. Note, howev-
er, that capacity is also reduced. The five values for 460 VAC opera-
tion are: 15, 17, 19, 21, or 23 amperes. The factory default setting is
21 amperes.
This is the value in percent to which the system will dehumidify or hu-
midify. There are configuration variables that determine whether dehu-
midification/humidification capabilities are installed. In the test mode,
the setpoint will be temporarily set to 1%, allowing the test of dehumid-
ification. After 5 minutes, the normal setpoint is restored.
If unit is configured for HUMIDIFICATION MODE then selection of a
setpoint greater than 75% will activate humidification, and a setpoint
less than or equal to 75% will activate dehumidification. If the unit is
configured for dehumidification only, then the entire setpoint range will
apply to dehumidification. If Pretrip is initiated, this value will be set to
"OFF" automatically.
(Replaced by Cd48 interface if CnF50 Enhanced Bulb Mode Interface
is active.)
The current state of the economy mode option, "-----", On, or Off. CnF22
determines whether economy mode offered. Economy mode is a user
selectable mode of operation provided for power saving purposes.
4–29