Troubleshooting; Installation Checklist; Sequence Of Operation - American Water Heater 300 Series Instruction Manual

Commercial gas water heaters, power vent/power direct vent gas with direct spark ignition
Table of Contents

Advertisement

INSTALLATION CHECKLIST

The list below represents some of the most critical installation
requirements that, when overlooked, often result in operational
problems, down time and needless parts replacement. This is not
a complete list. Before performing any troubleshooting procedures
use the list below to check for installation errors. Costs to correct
installation errors are not covered under the limited warranty.
Ensure all installation requirements and instructions in this manual
have been maintained and followed.
WATER HEATER LOCATION
1. Ensure proper clearances to combustibles are maintained and
there is sufficient room to service the water heater.
2. Ensure the area is free of corrosive elements and flammable
materials.
VENTING
3. Ensure the intake air and/or vent (exhaust) piping is the correct
size for the installed length.
4. Ensure the maximum equivalent feet of pipe has not been
exceeded for the intake air and/or vent pipe.
5. Ensure the maximum number of elbows has not been exceeded
in the intake air and/or vent pipe.
6. Ensure all exterior clearances for the intake air, vent and
concentric terminations are maintained. These clearances and
those cited by local and national codes must be maintained.
7. If venting direct vent, ensure the screen located in air intake at
the water heater was removed.
GAS SUPPLY AND PIPING
8. Ensure the supply gas line to each water heater meets the
minimum supply gas line size requirements.
CONDENSATE DRAIN
9. Ensure the condensate drain is properly connected to the
exhaust elbow on the water heater and draining freely to a
suitable floor drain.
ELECTRICAL CONNECTIONS
10. Ensure the water heater is properly grounded. Flame sensing
requires an adequate earth ground. If the water heater is not
properly grounded it will cause Ignition Failure.
11. Ensure the power supply connections to the water heater are
polarity correct.

TROUBLESHOOTING

SEQUENCE OF OPERATION

Read the Sequence of Operation section before attempting
to correct any operational problems. Refer to Features and
Components (page 10) for the location of various water heater
components described in this section. See also the Sequence Of
Operation Flow Chart (page 53).
1.
When the control system is first powered, during boot up, it will
display water heater model information during initialization.
After a few moments the control system LCD Touch Display
which is part of the UIM (user interface module) will display
the default screen known as the "Desktop" screen.
2.
If the control system determines that the actual water
temperature inside the tank is below the programmed
Operating Set Point minus the Differential setting, a heating
cycle is activated.
3.
The control system then performs selected diagnostic system
checks. This includes confirming the blocked exhaust, blocked
intake and ECO (energy cut out) switch contacts are closed.
4.
If all diagnostic checks are successfully passed, the control
system energizes the Combustion Blower for pre-purge.
5.
The control system energizes the Spark Ignition Transformer..
6.
After a few seconds, the control system energizes the 24V
Gas Control Valve allowing gas to flow to the Main Burner.
7.
The control system monitors the flame sensor to confirm a
flame is present at the Main Burner. If a flame is not verified
during the ignition trial period the control system will try for
ignition up to two more times. If flame can not be verified after
three trials for ignition, the control system will lock out and
display the "Ignition Failure" Fault message.
8.
If a flame is verified, the control system will de-energize
the Spark Ignition Transformer and enter the heating mode
where it will continue heating the water until the Operating
Set Point is reached. At this point, the control system will
de-energize the 24-volt gas valve and enter the post-purge
cycle (approximately 60 seconds).
9.
The Combustion Blower will run for the duration of the
postpurge cycle to purge the water heater of all combustion
gases. When the post-purge cycle is complete, the blower is
de-energized and will coast to a stop.
10. The control system now enters the standby mode while
continuing to monitor the internal storage tank water
temperature and the state of other system devices. If the tank
temperature drops below the Operating Set Point minus the
Differential setting, the control will automatically return to Step
2 and repeat the operating cycle.
56

Advertisement

Table of Contents
loading

This manual is also suitable for:

301 series

Table of Contents