POLYPROPYLENE INSTALLATIONS

The water heater has been approved to be installed with
Polypropylene vent material as shown in Table 5 and Table 6. The
approved application of single wall, non-flexible, non-concentric
Polypropylene vent material is offered by two specific manufacturers
(Centrotherm ECO Systems and DuraVent Polypropylene). These
listed products must be installed by following the vent manufacturer's
instructions. Refer to Table 7 on Page 27 to determine the maximum
pipe length and number of elbows that can be used.
Insulation should not be used on Polypropylene venting materials.
The use of insulation will cause increased vent wall temperatures,
which could result in vent pipe failure.
Use only the adapters and vent system listed in Tables below. DO
NOT mix vent systems of different types or manufacturers. Failure
to comply could result in severe personal injury, death, or substantial
property damage.
Nominal Pipe
Flue Outlet Adapter
Diameter
2"
2PPS-AD
3"
3PPS-AD
Nominal Pipe
Flue Outlet Adapter
Diameter
ISAGL
2"
0202
ISAGL
3"
0303
Table 5
M & G Duravent PolyPro
Adapter
Ring
90 Degree
Connector
Connector
PPS-PAC
2PPS-LB
2PPS-E90
PPS-PAC
3PPS-LB
3PPS-E90
Table 6
Centrotherm InnoFlue SW
Adapter
Ring
90 Degree
Connector
Connector
IAFC02
IANS02
ISELL0287
IAFC03
IANS03
ISELL0387
Installations must comply with applicable national, state, and local
codes. For Canadian installation, Polypropylene vent must be
listed as a ULC-S636 approved system. If Polypropylene vent is
not required by your local code, you may use either PVC or CPVC
pipes for your water heater that allows non-metallic venting material
installations.
Polypropylene vent systems do not use cement to connect the pipe
and elbow sections but use a push together gasket seal method.
Do not attempt to connect Polypropylene with sealant cement. All
vent connections MUST be secured by the vent manufacturer's joint
connector. The installer must use a specific vent starter adapter at
the flue connection. The adapter is supplied by the vent manufacturer
to adapt to its vent system.
In order to be in full compliance with UL 1738 or ULC-S636 and to
meet the requirements of the water heater manufacturer, you must
use the metal joint connector rings, available from the Polypropylene
vent manufacturer, to stiffen the joints of 2", and 3" diameter pipes.
Vent Material
Elbow
2PPS
2PPS-E90 & 2PPS-BG for Intake (Direct Vent
3PPS
3PPS-E90 & 3PPS-BG for Intake (Direct Vent
Vent Material
Elbow
ISVL02
ISELL0287 & IASPP02 for Intake (Direct Vent
ISVL03
ISELL0387 & IASPP03 for Intake (Direct Vent
26
Terminal(s)
2PPS & 2PPS-BG for Exhaust;
only)
3PPS & 3PPS-BG for Exhaust;
only)
Terminal(s)
ISVL02 & IASPP02 for Exhaust;
only)
ISVL03 & IASPP03 for Exhaust;
only)