USER SETTINGS & CONTROL SYSTEM MENUS
TEMPERATURES MENU
Operating Set Point and Differential Adjustment
The Operating Set Point is adjustable from 90°F (42°C) to 181°F
(83°C). The factory setting is 120°F (49°C). The Differential is
adjustable from 2° to 20°. The factory setting is 8°. These user
settings are accessed from the Temperatures menu. The following
instructions explain how to adjust these settings and navigate the
control system menus.
When the water temperature, sensed by the control system
from the Temperature Probe, reaches the Operating Set Point,
Temperatures Menu
From the Desktop screen, press MENU. The "Main Menu" screen will be
displayed.
The Main Menu is where all control system menus are listed, see Table 20
on page 43 for a complete list and description of control system menus.
Use the Up and Down slidebar to view all control system menus from the
Main Menu.
Press "Temperatures" to access the Temperature menu.
Press "Operating Setpoint" to access the temperature setpoint menu.
Press "CHANGE" to activate the adjustment mode for this menu item.
NOTE: Higher Temperature settings increase wear and operating costs.
Set the Operating Set Point to the lowest setting which produces an
acceptable hot water supply. This will always provide the most energy
efficient operation and longer life.
Use the "+" and "-" Buttons to change the current setting.
Press "ACCEPT" to save the new setting. Press "BACK" to discard changes
and return to the previously saved setting.
Note: Use this procedure to change the Differential setting and other
adjustable user settings in the control system menus.
Description/Action
the control system ends the heating cycle. A heating cycle is
activated again when the sensed water temperature drops below
the Operating Set Point minus the Differential setting.
NOTE: Lower Differential settings may cause excessive heating
cycles (short-cycling) which can cause premature failure of heater
components. Set the Differential at the highest setting which
produces an acceptable hot water supply. Set the Operating Set
Point to the lowest setting which produces an acceptable hot
water supply for most efficient use.
MANUFACTURER / MODEL INFORMATION
Operating Setpoint
Status: Standby
MENU
Temperatures
Heater Status
Display Settings
Heater Information
Current Fault
Operating Setpoint
Differential
Tank Probe Offset
Operating Setpoint
MIN
°
90
F
ACCEPT
44
Display
Main Menu
BACK
Temperatures
120°F >
8°F >
0°F >
BACK
°
120
F
MAX
°
160
F
BACK
120°F
HELP
>
>
>
>
>
HELP
HELP

Advertisement

Table of Contents
loading

This manual is also suitable for:

301 series

Table of Contents