12.4
8 READ/WRITE CONFIGURATION BITS
SUPPORTS WRITE SINGLE ONLY
READABLE IN MULTIPLES OF 8 BITS
STARTING AT 8 BIT BOUNDARIES
ADDRESS
FUNCTION
00001
DISK ON CAM=0 CRANK=1
00002
TEST FOR PROPER DISK YES=1
00003
ENABLE SECONDARY DIAGS YES=1
00004
ENERGY BIT0 00= ~ 160 01= ~ 170
00005
ENERGY BIT1 10= ~ 180 11= ~ 190
00006
SLAVE
00007
reserved
00008
OFF = MAGNETIC Pickup
12.5
4 READ/WRITE REGISTERS MIRROR COIL BITS
ADDRESS
FUNCTION
40001
REG40001=CoilBits 00016-00001
40002
REG40002=CoilBits 00032-00017
40003
REG40003=CoilBits 00048-00033
40004
REG40004=CoilBits 00064-00049
12.6
8 READ/WRITE REGISTERS REGARDING APPLICATION
ADDRESS
FUNCTION
40005
Disk+1
40006
Disk Lineup to TDC xx.x DEG
40007
Insertion Ret MIN=2.0 DEG xx.x
40008
Purge Delay Cycles 0-255
40009
RPM Over Speed Setpoint
40010
RPM Crank to Run Threshold
40011
Low Supply Voltage Limit xx.xV
40012
SLAVE ANGLE xx.x DEG
12.7
12 READ/WRITE REGISTERS FOR CYLINDER RET. TABLE
ADDRESS
FUNCTION
40017
OUTPUT A EXTRA RETARD
40018
OUTPUT B EXTRA RETARD
40019
OUTPUT C EXTRA RETARD
40020
OUTPUT D EXTRA RETARD
40021
OUTPUT E EXTRA RETARD
40022
OUTPUT F EXTRA RETARD
40023
OUTPUT K EXTRA RETARD
40024
OUTPUT L EXTRA RETARD
40025
OUTPUT M EXTRA RETARD DEG
CD200D II 4-17 All rights reserved © ALTRONIC, LLC 2017
ON = HALL-EFFECT Pickup
2,3,4,5,6,7,8,9,10,12
DEG
DEG
DEG
DEG
DEG
DEG
DEG
DEG
14