Connection Restrictions for 100BASE-TX Repeater HUBs

Up to two stages of cascade connections are possible with Class II 100BASE-TX repeater HUBs. In
addition, the maximum total length of cables (1) (2) (3) is 205m or less. For details, refer to the user's
manual for the 100BASE-TX repeater HUB used.
Figure 4.2. Connection restrictions for 100BASE-TX repeater HUBs (Class II)

Connection Restrictions for 10BASE-T Repeater HUBs

As many as four stages of 10BASE-T repeater HUBs can be connected using cascade connection. In
addition, the length of UTP or STP cable between cascaded HUBs is 100m or less. For details, refer to the
user's manual for the 10BASE-T repeater HUB used.
Figure 4.3. Connection restrictions for 10BASE-T repeater HUBs