Technical Specification

Product
Ignition Type
Ignition Source
High Voltage Cable
Maximum Length
Flame Sense Cable
Maximum Length
Flame Detection Means
Flame Detection Type
Minimum Flame Current
Flame Failure Response
Time
Maximum Spark Gap
Number of Trials Before
100% Shutoff
Trial-for-Ignition Time
Prepurge Time
Inter-Purge Time
Automatic Recycle Delay
Period
Power Requirements
Contact Rating
Wiring Connections
Maximum Firing Rate
Ambient Operating and
Storage Temperature
Humidity
Type of Gas
Packaging
Pack Weight
Agency Listing
Specifications Standards
The performance specifications are nominal and conform to acceptable industry standards. All agency certification of BASO products is
performed under dry and controlled indoor environmental conditions. Use of BASO products beyond these conditions is not recommended and
may void the warranty. If the product is exposed to water (dripping, spraying, rain, etc.) or other harsh environments, it must be protected. The
original equipment manufacturer or end user is responsible for the correct application of BASO products. For questionable applications, please
consult BASO Gas Products LLC. BASO Gas Products LLC shall not be liable for damages or product malfunctions resulting from
misapplication or misuse of its products.
1007 South 12th Street
PO Box 170
Watertown, WI 53094
1-877-227-6427
BG1600M Intermittent Pilot Ignition Control with Rollout Switch Installation Instructions
BG1600M Intermittent Pilot Ignition Control with Rollout Switch
Indirect
High voltage spark, capacitive discharge
48 in. (1,220 mm) (Resistive wire recommended, rated for at least 15kV.)
48 in. (1,220 mm)
Flame Rectification
Remote
0.15 microamperes
2 seconds maximum
0.2 in. (5.1 mm)
One
85 seconds
0 or 15 seconds
15 seconds
None or 5 minutes
Control:
24 VAC (+10%/-15%), 50/60 Hz
Operation Current:
0.2 A nominal + valves
Main Valve:
4 A maximum
Pilot Valve:
2 A maximum
1/4 in. (6.35 mm) male spade
400,000 Btu/hr (117 kW)
-40 to 170°F (-40 to 77°C)
95% RH noncondensing
Natural, Liquefied Petroleum (LP), Manufactured, Mixed or LP Gas-Air Mixture
Individual pack (1 per box)
Individual overpack (20 per box)
Individual pack 1 lb (.454 kg)
Individual overpack 18 lb (8.17 kg)
CSA Certificate Number Pending
ANSI Standard Z21.20
CAN/CSA-C22.2 No. 199
Published in U.S.A.
www.baso.com