6.2.11 6-** Analog In/Out

Parameter
Parameter Description
Number
6 - 00
Live Zero Timeout Time
6 - 01
Live Zero TimeoutFunction
6 - 10
Terminal 53 Low Voltage
6 - 11
Terminal 53 High Voltage
6 - 12
Terminal 53 Low Current
6 - 13
Terminal 53 High Current
6 - 14
Terminal 53 Low Ref./Feedb. Value
6 - 15
Terminal 53 High Ref./Feedb. Value
6 - 16
Terminal 53 Filter Time Constant
6 - 19
Terminal 53 mode
6 - 22
Terminal 60 Low Current
6 - 23
Terminal 60 High Current
6 - 24
Terminal 60 Low Ref./Feedb. Value
6 - 25
Terminal 60 High Ref./Feedb. Value
6 - 26
Terminal 60 Filter Time Constant
6 - 81
Keypad potentiometer Low Ref.
6 - 82
Keypad potentiometer High Ref.
6 - 90
Terminal 42 Mode
6 - 91
Terminal 42 Analog Output
6 - 92
Terminal 42 Digital Output
6 - 93
Terminal 42 Output Min Scale
6 - 94
Terminal 42 Output Max Scale

6.2.12 7-** Controllers

Parameter
Parameter Description
Number
7 - 20
Process CL Feedback 1 Resource
7 - 30
Process PI Normal/ Inverse Control
7 - 31
Process PI Anti Windup
7 - 32
Process PI Start Speed
7 - 33
Process PI Proportional Gain
7 - 34
Process PI Integral Time
7 - 38
Process PI Feed Forward Factor
7 - 39
On Reference Bandwidth

6.2.13 8-** Comm. and Options

Parameter
Parameter Description
Number
8 - 01
Control Site
8 - 02
Control Word Source
8 - 03
Control Word Timeout Time
8 - 04
Control Word Timeout Function
8 - 06
Reset Control Word Timeout
8 - 30
Protocol
8 - 31
Address
8 - 32
GE Drive Port Baud Rate
8 - 33
GE Drive Port Parity
8 - 35
Minimum Response Delay
8 - 36
Max Response Delay
8 - 50
Coasting Select
8 - 51
Quick Stop Select
8 - 52
DC Brake Select
8 - 53
Start Select
8 - 54
Reversing Select
8 - 55
Set-up Select
8 - 56
Preset Reference Select
8 - 94
Bus feedback 1
AF-60 LP™ Micro Drive Operating Instructions
Default Value
2 Setup
10 s
All set-ups
[0] Off
All set-ups
0.07 V
All set-ups
10 V
All set-ups
0.14 mA
All set-ups
20 mA
All set-ups
0
All set-ups
50
All set-ups
0.01 s
All set-ups
[0] Voltage mode
1 set-up
0.14 mA
All set-ups
20 mA
All set-ups
0
All set-ups
50
All set-ups
0.01 s
All set-ups
0
All set-ups
50
All set-ups
[0] 0-20 mA
All set-ups
[0] No operation
All set-ups
[0] No operation
All set-ups
0%
All set-ups
100%
All set-ups
Default Value
2 Setup
[0] No function
All set-ups
[0] Normal
All set-ups
[1] Enabled
All set-ups
0 Hz
All set-ups
0.01
All set-ups
9999 s
All set-ups
0%
All set-ups
5%
All set-ups
Default Value
2 Setup
[0] Digital and ctrl.word
All set-ups
[1] GE Drive RS485
All set-ups
1 s
1 set-up
[0] Off
1 set-up
[0] No function
1 set-up
[0] GE Drive
1 set-up
1
1 set-up
[2] 9600 Baud
1 set-up
[0] Even Parity 1 Stop Bit
1 set-up
0.01 s
1 set-up
5 s
1 set-up
[3] Logic OR
All set-ups
[3] Logic OR
All set-ups
[3] Logic OR
All set-ups
[3] Logic OR
All set-ups
[3] Logic OR
All set-ups
[3] Logic OR
All set-ups
[3] Logic OR
All set-ups
0
All set-ups
DET-579A
Change During
Conver-
Type
Operation
sion
Index
TRUE
0
Uint8
TRUE
-
Uint8
TRUE
-2
Uint16
TRUE
-2
Uint16
TRUE
-2
Uint16
TRUE
-2
Uint16
TRUE
-3
Int32
TRUE
-3
Int32
TRUE
-2
Uint16
TRUE
-
Uint8
TRUE
-2
Uint16
TRUE
-2
Uint16
TRUE
-3
Int32
TRUE
-3
Int32
TRUE
-2
Uint16
TRUE
-3
Int32
TRUE
-3
Int32
TRUE
-
Uint8
TRUE
-
Uint8
TRUE
-
Uint8
TRUE
-2
Uint16
TRUE
-2
Uint16
Change During
Conver-
Type
Operation
sion
Index
TRUE
-
Uint8
TRUE
-
Uint8
TRUE
-
Uint8
TRUE
-1
Uint16
TRUE
-2
Uint16
TRUE
-2
Uint32
TRUE
0
Uint16
TRUE
0
Uint8
Change During
Conver-
Type
Operation
sion
Index
TRUE
-
Uint8
TRUE
-
Uint8
TRUE
-1
Uint16
TRUE
-
Uint8
TRUE
-
Uint8
TRUE
0
Uint8
TRUE
0
Uint8
TRUE
-
Uint8
TRUE
-
Uint8
TRUE
-3
Uint16
TRUE
-3
Uint16
TRUE
-
Uint8
TRUE
-
Uint8
TRUE
-
Uint8
TRUE
-
Uint8
TRUE
-
Uint8
TRUE
-
Uint8
TRUE
-
Uint8
TRUE
0
Int16
6
51