3.4.2 Connecting to Control Terminals

This illustration shows all control terminals of the frequency converter. Applying Start (term. 18) and an analog reference (term. 53 or 60) make the frequency
converter run.
3
Illustration 3.7: Overview of control terminals in PNP-configuration and factory setting.

3.5 Switches

NB!
Do not operate switches with power on the frequency converter.
Bus termination:
Switch BUS TER pos. ON terminates the RS485 port, terminals 68, 69. See
power circuit drawing.
Default setting = Off.
S200 Switches 1-4:
Switch 1:
*OFF = PNP terminals 29
ON = NPN terminals 29
Switch 2:
*OFF = PNP terminal 18, 19, 27 and 33
ON = NPN terminal 18, 19, 27 and 33
Switch 3:
No function
Switch 4:
*OFF = Terminal 53 0 - 10 V
ON = Terminal 53 0/4 - 20 mA
* = default setting
Table 3.3: Settings for S200 Switches 1-4
16
AF-60 LP™ Micro Drive Operating Instructions
Illustration 3.8: S640 Bus termination.
Illustration 3.9: S200 Switches 1-4.
NB!
Parameter 6-19 must be set according to Switch 4 position.
DET-579A