Bacnet Mstp Quick Start - Greenheck 474706 Reference Manual

Ddc controller for tempered air products
Table of Contents

Advertisement

The card is loaded with the following default BACnet
MSTP parameters.
Parameter
Factory
Device Instance
77000
Station Address
0
Max Master
127
Max Info Frames
20
Baudrate
38400
G.
Service
c. BMS Config
BMS Configuration
Protocol:
BACnet MSTP
BACnet Plugin?
YES
MSTP SETUP
Instance:
77000
Baudrate
38400
MAC Addr:
MaxMasters:
127
MaxInfoFrames:
20
BACnet Read/Write
Function:
Read
Update?
Yes
*Cycle unit power to confirm
write command.
2. Go to BMS Config menu and view BACnet Read/
Write screen.
3. Change Function to Read and Update? to YES.
Current BACnet MSTP parameters should now be
displayed in the BACnet MSTP SETUP screen. If
all values appear to be zeros, consult the factory.
(Make sure you have allowed several minutes for the
controller to initialize). *Values may appear to be zero
prior to setting the Function to READ.
To change BACnet MSTP parameters:
1. Power on the controller and allow several minutes
to initialize.
2. Go to BMS Config menu and view MSTP SETUP
screen.
3. Move cursor to desired parameter by pressing the
Prg
Prg
Esc
Prg
Esc
buttons. Press
Prg
Esc
to change. Press the
parameter. Press
to save adjusted value.
®

BACnet MSTP Quick Start

Minimum
Maximum
0
4194303
0
127
0
127
0
255
9600-19200-38400-76800
To view the current
parameters, go the BMS
Config menu within the
controller by pressing
the
key.
Prg
Esc
To access the BMS
Config sub-menu, enter
the service-password
(Default=1000).
Protocol must be
BACnet MSTP and
BACnet Plugin must be
YES.
Prg
Esc
Press the
button
arrow to view next
0
screen.
Current BACnet MSTP
parameters should be
displayed. If values
appear to be zero, follow
the procedure below.
To read current settings:
1. Power on controller
and allow several
minutes to initialize.
Esc
to select the parameter
Prg
Esc
Prg
Esc
buttons to adjust the
4. Once desired parameters have been entered, go
to BACnet Read/Write screen. Change Function to
Write and Update? to YES.
5. Reboot the controller by cycling power to the unit.
Allow several minutes for the controller to initialize.
6. View MSTP parameters. If changed values did not
save, contact the factory.
The communication card
is located in the Serial
Card port on the face of
the controller. The card
includes two sets of LED
lights for communication
troubleshooting.
Status LED: Indicates the status of communication
between the card and controller.
• Q uick green-off-green if communication with
controller is ok.
• S low red-off-red if communication is not
established.
RS485 LED: Indicates the status of communication
with the BACnet MSTP network. Wait for 40 seconds
to determine status of communication.
• Green with occasional red, communication is OK.
• G reen and red both on, communications is not
established.
Communication Troubleshooting
See Carel Data sheet for more info.
If attempting to communicate with the controller over
BACnet MSTP, refer to the card LEDs for system
information.
Status LED slow red blink
• Confirm card is firmly plugged in.
• C onfirm BMS Protocol is set to BACnet MSTP.
RS485 LED green and red both on
• Confirm system and card baudrate are the same.
• C onfirm card Max Master is equal to or greater
than the Station (MAC) Address of the Master with
the highest address.
Recalling Factory Parameters
Follow this procedure to revert to factory parameters
for one power cycle. When restarted, the card will
resume using the previous user parameters.
1. With controller off, hold the push button located
on the BACnet MSTP card, while powering the
controller back on.
2. Continue to hold the button, while watching the
Status LEDs. Wait for the Status LEDs to blink red
slowly, and release before the third slow flash.
3. Wait for about one minute for the factory
parameters to be loaded.
DDC Controller for Tempered Air Products
Status LED
RS485 LED
Push Button
29