Service Settings; Working Hour Set; Probe Adjustment; Password/Defaults - Greenheck 474706 Reference Manual

Ddc controller for tempered air products
Table of Contents

Advertisement

Unit BMS Control
Unit Start/Stop:
No
Temp Setpoint:
Local
Occupancy:
Input ID6
BMS Writable Points
TempSetpoint:
78.0°F
Start/Stop:
Stop
Reset Alarms:
No
Occupancy:
Occ
G.
Service
d. Service Settings
a. Working hour set
b. Probe adjustment
b. Password/Defaults
MAINTENANCE HOURS
SYSTEM
Run hours:
0000h
Set Point:
0000h
Reset to Zero?
No
Analog Input
Outside Temperature
Input B01
Offset:
0.0°F
Value:
70.5°F
User Default
Insert new service password
(PW1):
1000
User Default Settings
Save?
No
Restore?
No
20
DDC Controller for Tempered Air Products
T
his screen allows The user To quickly enable The
.
operaTion
This screen appears if the unit is equipped with a BMS communication card.
The factory default configuration is for a non-BMS controlled unit. To allow
the BMS to start/stop the unit, change set point and occupancy, alter the
parameters on this screen.
T
his screen allows The user To view The sTaTus of The wriTable
View the status of each point to confirm BMS communication.
The Service Settings menu allows the user to change the default Service
Password (1000), save and restore default parameters, and adjust probe
values.
T
his screen allows The user To view uniT run hours
.
for mainTenance
Run hours: The amount of time in hours that the unit has been powered.
Set Point: The amount of running time in hours before a maintenance alarm
should occur.
Reset to Zero: Reset the measured amount of run time.
T
p
a
he
robe
djusTmenT menu allows The user To calibraTe sensor probes
.
wiTh an offseT value
Similar screens are available for remaining sensor probes.
T
his screen allows The user To change The
T
his screen allows The user To
parameTers sTored in memory
If the user would like to save their settings, move the cursor to the SAVE
position and change to YES. This will save all of the current parameters into
memory as Service Settings. If the user would like to restore to these values
at some point in the future, moving the cursor to the RESTORE position, and
selecting YES will restore the controller to the user saved defaults.
bms
,
s
l
ervice
save
resTore
and
.
To conTrol uniT
bms
.
poinTs
and alTer seT poinTs
(pw1)
evel password
The defaulT
®