Bms Config - Greenheck 474706 Reference Manual

Ddc controller for tempered air products
Table of Contents

Advertisement

I/O Manual Management
END OF OVERRIDE MENU
Press ENTER to go to
I/O Manual Management
menu.
Analog Input
Outside Temperature Manual
Control B01:
ON
Manual Position
290
Value
84.2°F
G.
Service
c. BMS Config
BMS Configuration
Protocol:
BACnet MSTP
BACnet Plugin?
YES
MODBUS SETUP
Address:
Baudrate
9600
18
DDC Controller for Tempered Air Products
T
his screen allows The user To enTer The
The Manual Management menu allows the user to manually control the I/O
of the controller. The user can manually input values for the analog inputs
and digital inputs. The user can also manually control the analog outputs
and digital outputs. EXTREME CAUTION should be used when manually
controlling the I/O. It is highly recommended that manual control of the I/O
is done only with factory assistance. The controller's safeties and lockouts
are bypassed by this manual management and should only be used as
a troubleshooting feature. If the controller is powered down, I/O Manual
Management is reset to off. Therefore, if using this troubleshooting feature, the
best way to clear manually input values is to power down the controller.
T
his screen is an example of a manually managed TemperaTure analog inpuT
To manually control an analog input, change Manual Control to ON. Move
cursor to Manual position and alter value. The altered value will be displayed
below.
Similar screens exist for the remaining I/O. Contact the factory for more
details.
The BMS Config menu allows the user to view and alter BMS protocol settings.
If the BMS protocol is BACnet or Modbus, additional screens allow further
configuration. See below for details. To access the BMS Config sub-menu,
enter the service password (Default=1000).
T
his screen allows The user To selecT The
proTocols require a communicaTions card insTalled in The
,
porT
locaTed on The face of The conTroller
If the protocol is BACnet MSTP or BACnet IP/Eth, the user can change
common BACnet parameters via the controller. The BACnet Plugin must be set
to YES.
T
his screen allows The user To adjusT
This screen only appears if the selected BMS protocol is set to Modbus
1
The address is the Modbus address of the card installed in the SERIAL CARD
port located on the face of the controller. (Factory Default Address = 1).
The Baud Rate should be set to the BMS baud rate (Factory Default Baud Rate
is 9600).
i/o m
m
anual
anagemenT menu
bms
. a
proTocol
ll
serial card
.
m
.
odbus parameTers
.
.
bms
.
®