Trial Operation - Daikin FTK(X)M-P Series Service Manual

Inverter pair wall mounted type
Table of Contents

Advertisement

Trial Operation

2. Trial Operation

Outline
Carry out the trial operation in accordance with the operation manual to ensure that all functions
and parts, such as flap movement, are working properly.
Trial operation should be carried out in either cooling or heating operation.
Detail
1. Measure the power supply voltage and make sure that it falls within the specified range.
2. In cooling operation, select the lowest programmable temperature (18°C); in heating
ARC466 Series
(1) Press the On/Off button to turn on the system.
(2) Press the center of the Temp button and the Mode button at the same time.
(3) Select T (trial operation) with the Temp
(4) Press the Mode button to start the trial operation.
(5) Press the Mode button and select operation mode.
(6) Trial operation terminates in approximately 30 minutes and switches into normal mode. To
93
operation, select the highest programmable temperature (30°C).
Trial operation may be disabled in either operation mode depending on the room
temperature.
After trial operation is complete, set the temperature to a normal level (26°C ~ 28°C in
cooling, 20°C ~ 24°C in heating operation).
For protection, the system does not start for 3 minutes after it is turned off.
quit trial operation, press the On/Off button.
(2) (4) (5)
or Temp
button.
(3)
(2) (3)
(1) (6)
(R19935)
Trial Operation and Field Settings
SiMT041509E