Warning; Features; Important Safeguards - Philips DYNALITE DMC4 Installation Instructions Manual

Modular controller (4 output modules)
Table of Contents

Advertisement

Features

Four Control Module Locations
Wide range of interchangeable control modules
available to meet the capacity and control type
needs of any project.
Modules supplied separately.
The DMC4 is only compatible with Philips
Dynalite modules.
Communication Module
Allows the controller to be used with a variety of
supported protocols.
Convection Cooled
The DMC4 is ventilated, and requires no active
cooling system when installed in accordance with
these instructions.
Multiple Control Options
The DMC4 is designed to operate as part of a
network system that can be structured to meet the
project's needs.
Simple Installation
The enclosure is suitable for both surface and
recess mount. Cabling knockouts for supply and
load cables are provided at the top, side and
back of the enclosure for supply and load cables.
Cabling knockouts for Control cables (Class 2 /
SELV) are located at the bottom of enclosure.
2
DMC4 Installation Instructions Rev 02

Important Safeguards

Read the Instructions – We recommend that you
read this instruction manual prior to commencement of
installation. Do not energize the DMC4 until all steps of
the installation procedure on page 6 are complete.
Compliance – The temperature limits and carrying
capacity of communication wires must comply with HD
384.5.523 and the installation of home and building
automation and control systems must comply with HD
60364-4-41.The network topology for installation is Daisy
Chain.
Special Programming – Once assembled, powered
and terminated correctly, this device will operate in basic
mode. A new Philips Dynalite user interface on the same
network will turn all output lighting channels on from
button 1 and off from button 4 allowing testing of network
cables and terminations. Advanced functions and custom
presets can then be configured via the EnvisionProject
commissioning software.
If commissioning services are required, contact your local
distributor for details.
Power Sources – This device should only be operated
from the type of supply specified on installed modules.
This device must be earthed.
High Voltage Insulation Test – Do not apply High
Voltage Insulation Test to any circuitry connected to the
dimming system, as damage to the electronics may result.
Mounting Location – This device must be mounted
upright on a vertical surface (refer to page 4 for mounting
instructions). The specified minimum clearance of
200mm (8") for all sides must be adhered to. Install in a
dry, well-ventilated location.
Audible Noise – Controllers may emit some audible noise
such as humming or relay chatter. Take this into account
when deciding the mounting location.
Data Cable – The recommended cable for connections
to the serial port is screened stranded RS485 compatible
CAT-5E data cable with three twisted pairs. Refer to the
installation instructions for the communication module for
more cabling information. This cable must be segregated
from mains and Class 1 cables as per local electrical
code. If anticipated cable runs are over 300 m (1000 ft) for
serial cables, consult your dealer for advice. Do not cut or
terminate live data cables.