Parts Arrangement; Setting The Unit - Lennox HSXA19 SERIES Installation Instructions Manual

Hide thumbs Also See for HSXA19 SERIES:
Table of Contents

Advertisement

Parts Arrangement

operation monitor
run capacitor
start capacitor
(HSXA19−024)
discharge line
compressor terminal plug
two−stage compressor

Setting the Unit

CAUTION
In order to avoid injury, take proper precaution when
lifting heavy objects.
Refer to unit dimensions for sizing mounting slab, plat-
forms or supports. Refer to figure 2 for installation clear-
ances.
Installation Clearances
NOTE − A service access
clearance of 30" (762 mm)
must be maintained in front
of the service access panel.
Clearance to one side must
be 36" (914 mm). Clearance
to one of the remaining two
sides may be 12" (304 mm)
and the final side may be 6"
(152 mm).
NOTE − A clearance of 24" (610 mm)
must be maintained between two units.
NOTE − 48" (1219 mm) clearance required on top
of unit. Maximum soffit overhang is 36" (914 mm).
Figure 2
system
vapor line
high pressure switch
low pressure switch
as noted
30"
as
(762 mm)
noted
as
noted
filter drier
Figure 1
A − Slab Mounting
When you install the unit at grade level, the top of the slab
should be high enough above the grade so that water from
higher ground will not collect around the unit. See figure 3.
Slab should have a slope tolerance away from the building
of 2 degrees or 2 inches per 5 feet (51 mm per 1.5 m). Refer
to the next section (roof mounting) for barrier construction if
the unit must face prevailing winter winds.
2 degrees or
2 in. per 5 foot
(51 mm per 1.5 m)
slope tolerance away
from building structure
ground level
Page 3
outdoor fan
(variable speed
on HSXA19−038)
contactor
vapor valve and
gauge port
Slab Mounting
discharge air
building
structure
mounting
slab
Figure 3