ABB ACS480 Quick Installation And Start-Up Manual page 2

General purpose drives

Advertisement

8. Install the control panel
To install the control panel:
1.
Close the front cover and tighten the
locking screw.
2.
Put the bottom edge of the control
panel into position.
3.
Push the top of the control panel until
it locks into position.
9. Start up the drive
For information on the start-up and drive parameters, refer to the ACS480 Firmware
manual (3AXD50000047399 [EN]).
WARNING! Before you start up the drive, make sure that the installation is
complete. Make sure that the cover of the drive and the cable box, if
included, are in place.
Make sure that the motor does not cause danger when it starts. Disconnect
the motor from other machinery, if there is a risk of damage or injury.
For information on the user interface, refer to
the ACS-AP-x Assistant control panel user's
manual (3AUA0000085685 [EN]).
The control panel has softkeys below the
display to access the corresponding
commands, and arrow keys to navigate the
menu and change parameter values. Push
the "?" button to open the help function.
First start-up:
Make sure that you have the motor data (from
the name plate) available.
1.
Set the main power to on.
2.
Select the user interface language with
the arrow keys and set it with the right
softkey (OK).
3.
Select Start set-up and push the right
softkey (Next).
4.
Select the localization and push the right
softkey (Next).
5.
To complete the start-up procedure, enter
the settings and values when you are
prompted by the set-up assistant.
To set up fieldbus communications for a
fieldbus adapter, refer to the applicable
fieldbus adapter manual and to the ACS480
Firmware manual (3AXD50000047399 [EN]).
You can also use Primary settings in the Main
menu to configure the unit.
Fieldbus communications
You can connect the drive to a serial communication link via a fieldbus adapter
module or the embedded fieldbus interface. The embedded fieldbus interface is
included in the I/O module, and it supports the Modbus RTU protocol. The table
shows the minimum set of parameters for embedded Modbus communication. For the
fieldbus adapter module settings, refer to the appropriate documentation.
Note! Embedded Modbus is valid with the I/O module.
To configure embedded Modbus communications:
1.
Connect the fieldbus cable and the required I/O signals. Refer to
connections (ABB standard
macro).
2.
If it is necessary, set the termination switch to ON.
3.
Power up the drive.
4.
Select the ABB limited 2-wire macro from Primary settings or with parameter
96.04.
5.
Configure fieldbus communications from the parameter list.
The minimum parameters that apply to embedded Modbus RTU:
Parameter
Setting
20.01 Ext1 commands
Embedded fieldbus
20.03 Ext1 in 1 source
Selected
28.11 Ext1 frequency ref1 (scalar)
EFB ref1
31.11 Fault reset selection
DI1
58.01 Protocol enable
Modbus RTU
58.03 Node address
1 (default)
58.04 Baud rate
19,2 kbps (default)
58.05 Parity
8 EVEN 1 (default)
6.
If you need to change other parameters, you can set them manually. Refer to the
ACS480 Firmware manual (3AXD50000047399 [EN]) and the applicable fieldbus
adapter documentation.
Warnings and faults generated by the drive
Warning
Fault
A2A1
2281
A2B1
2310
A2B3
2330
A2B4
2340
3130
3181
A3A1
3210
A3A2
3220
3381
A5A0
5091
6681
7510
A7AB
AFF6
FA81
FA82
For the complete list of warnings and faults, refer to the ACS480 Firmware manual
(3AXD50000047399 [EN]).
Ratings
For detailed technical information, refer to the ACS480 Hardware manual
(3AXD50000047392 [EN]).
IEC ratings
Type
Input
ACS480-
rating
04-
?
I
1N
A
Stop
Loc/Rem
Start
3-phase U
= 380...440 V
N
02A7-4
4.2
03A4-4
5.3
04A1-4
6.4
05A7-4
9.0
07A3-4
11.5
09A5-4
15.0
12A7-4
20.2
018A-4
27.2
026A-4
40.0
033A-4
45.0
039A-4
50.0
046A-4
56.0
050A-4
60.0
NEMA ratings
Type
ACS480-04-
3-phase U
= 460 V (440...480 V)
N
02A7-4
03A4-4
04A1-4
05A7-4
07A3-4
09A5-4
12A7-4
018A-4
026A-4
033A-4
039A-4
046A-4
050A-4
Fuses
For more information on fuses, circuit breakers and manual motor protectors, refer to
the ACS480 Hardware manual (3AXD50000047392 [EN]).
Ambient conditions
Default I/O
Requirement
Installation altitude
Air temperature
Relative humidity
Contamination levels
(IEC 60721-3-3)
Shock (IEC 60068-2-27,
ISTA 1A)
Free fall
1) Up to 4000 m is possible for 400 V units, if the maximum switching voltage for the
integrated Relay Output 1 is 30 V at 4000 m (e.g. do not connect 250 V to Relay
Output 1). Up to 250 V is permitted up to 2000 m.
For a 3-phase 400 V drive at 2000...4000 m, only the following power systems are
permitted: TN-S, TN-c, TN-CS, TT (not corner earthed).
Description
Warning: Current calibration is done at the next start.
Fault: Output phase current measurement fault.
Overcurrent. The output current is more than the internal limit. This can be
caused by an earth fault or phase loss.
Earth leakage. A load unbalance that is typically caused by an earth fault
in the motor or the motor cable.
Short circuit. There is a short circuit in the motor or the motor cable.
Input phase loss. The intermediate DC circuit voltage oscillates.
Cross connecion. The input and motor cable connections are incorrect.
DC link overvoltage. There is an overvoltage in the intermediate DC circuit.
DC link undervoltage. There is an undervoltage in the intermediate DC
circuit.
Output phase loss. All three phases are not connected to the motor.
Safe torque off. The Safe torque off (STO) function is on.
EFB communication loss. Break in embedded fieldbus communication.
FBA A communication. Communication lost between drive and fieldbus
adapter.
Extension I/O configuration failure. I/O module is not installed into drive or
ABB limited macro is not selected.
Identification run. The motor ID run occurs at the next start.
Safe torque off 1. The Safe torque off circuit 1 is broken.
Safe torque off 2. The Safe torque off circuit 2 is broken.
Input
Max.
Output ratings
with
current
Nominal use
Light-duty use Heavy-duty use
choke
I
I
I
P
I
P
I
1N
max
N
N
Ld
Ld
Hd
A
A
A
kW
A
kW
A
2.6
3.2
2.6
0.75
2.5
0.75
1.8
3.3
4.7
3.3
1.1
3.1
1.1
2.6
4.0
5.9
4.0
1.5
3.8
1.5
3.3
5.6
7.2
5.6
2.2
5.3
2.2
4.0
7.2
10.1
7.2
3.0
6.8
3.0
5.6
9.4
13.0
9.4
4.0
8.9
4.0
7.2
12.6
16.9
12.6
5.5
12.0
5.5
9.4
17.0
22.7
17.0
7.5
16.2
7.5
12.6
25.0
30.6
25.0
11.0
23.8
11.0
17.0
32.0
45.0
32.0
15.0
30.5
15.0
25.0
38.0
57.6
38.0
18.5
36.0
18.5
32.0
45.0
68.4
45.0
22.0
42.8
22.0
38.0
50.0
81.0
50.0
22.0
48.0
22.0
45.0
3AXD10000299801.xls
Input
Input
Output ratings
rating
with
Nominal use
Heavy-duty use
choke
I
I
I
P
I
1N
1N
Ld
Ld
Hd
A
A
A
hp
A
3.4
2.1
2.1
1.0
1.6
4.8
3.0
3.0
1.5
2.1
5.4
3.4
3.4
2.0
3.0
7.7
4.8
4.8
2.0
3.4
9.6
6.0
6.0
3.0
4.0
12.2
7.6
7.6
5.0
4.8
17.6
11.0
11.0
7.5
7.6
22.4
14.0
14.0
10.0
11.0
33.6
21.0
21.0
15.0
14.0
37.9
27.0
27.0
20.0
12.0
44.7
34.0
34.0
25.0
27.0
49.8
40.0
40.0
30.0
34.0
50.4
42.0
42.0
30.0
40.0
3AXD10000299801.xls
During operation (installed for stationary use)
230 V units: 0...2000 m above sea level (with derating above 1000 m)
400 V units: 0...4000 m above sea level (with derating above 1000 m)
-10...+50 °C (14...122 °F). Up to +60 °C with derating.
No frost allowed.
Up to 95% without condensation
Class 3C2
Class 3S2
Not allowed
Not allowed
Dimensions and weights
D
H1
H2
H3
mm
in
mm
in
mm
in
R1
205 8.07 223 8.78 176 6.93
R2
205 8.07 223 8.78 176 6.93
R3
205 8.07 220 8.66 176 6.93 172 6.76 207 8.15 148 5.83 191 7.52 3.52 7.76
R4
205 8.07 240 9.45 176 6.93 260 10.24 212 8.35 238 9.37 191 7.52 6.02 13.3
Free space requirements
Frame size
Above
mm
in
R1...R4
75
2.95
Certifications
The applicable certifications are shown on the product's type label.
Frame
size
P
Hd
CE marking
EAC marking
kW
Declaration of conformity
0.55
R1
0.75
R1
1.1
R1
1.5
R1
2.2
R1
3.0
R1
4.0
R2
5.5
R3
7.5
R3
11.0
R4
15.0
R4
18.5
R4
22.0
R4
Frame
size
P
Hd
hp
0.75
R1
1.0
R1
1.5
R1
2.0
R1
2.0
R1
3.0
R1
5.0
R2
7.5
R3
10.0
R3
15.0
R4
20.0
R4
25.0
R4
30.0
R4
Related documents
Document
ACS480 Hardware manual
(1
ACS480 Firmware manual
ACS480 Quick installation and start-up guide
FDNA-01 DeviceNet adapter module quick guide
FENA-01/-11/-21 Ethernet adapter module user's manual
FMBT-21 Modbus/TCP adapter module quick guide
FPBA-01 PROFIBUS DP adapter module user's manual
FPNO-21 PROFINET adapter module quick guide
Online list of the manuals applicable to this product:
https://library.e.abb.com/public/
4a74c57b6bac4c2a953853639b6c80f6/
Link_List_ACS480.html
Online installation videos:
https://www.youtube.com/watch?v=L-rGHZ8I1zg
https://www.youtube.com/watch?v=nICGj9ntzA0
https://www.youtube.com/watch?v=0aTWO7U2fas
W
M1
Ø 5 [.21]
Ø 10 [.21]
M2
Ø 5 [.21]
Dimensions and weights
W
D
M1
M2
Weight
mm
in
mm
in
mm
in
mm
in
kg
lb
73
2.87 207 8.15
50 1.97 191 7.52 1.77 3.90
97
3.80 207 8.15
75 2.95 191 7.52 2.35 5.19
3AXD10000299801.xls
Free space required
Below
Sides
mm
in
mm
in
75
2.95
0
0
3AXD10000299801.xls
UL marking
TÜV Nord marking
RCM marking
Code (English)
3AXD50000047392
3AXD50000047399
3AXD50000047400
3AXD50000158515
3AUA0000093568
3AXD50000158560
3AFE68573271
3AXD50000158577