D I S T R I B U T I O N S O LU T I O N S
Room layout
IAC A-FL 12.5 kA filters
200 min
1070
Figure 27. Minimum distances from the walls of the installation room,
solution IAC A-FL 12.5 kA 1s with filters installed on each individual unit
ATTENTION
IAC A-FL version – Do not access the rear part of
the switchgear while this is under service
conditions. Compliance with the installation
distances is mandatory
(*) 1300 mm at least for panels with circuit-breaker
IAC A-FLR 16 kA against a wall
200 min
1000 min
(*)
Figure 28. Minimum distances from the walls of the installation room,
solution IAC A-FLR 16 kA 1s with filters installed on each unit
IAC A-FLR version – No access limitations to the
Swg Room. Installation distances to be respected
1070
1000 min
ATTENTION
15
(*)