Intelligent Valve Monitor
Sensor Functions Configuration Example:
For our example we will configure the sensor to learn
that the average time for valve actuation in 16 cycles
and 10% tolerance in time before indicating failure in
the function of intelligence. For our example the
software used for configuration is the ASI-Control
Tools.
1 - Attach the sensor according to the connection
diagram and connect a PC with the ASI-Control Tools
software installed.
2 - Place the dip number 3 to "ON", the sensor will
learn it the average time of operation of the valve 16
cycles.
3 - Place the dip number 5 to "ON" so that the
tolerance in time before indicating failure is 10%.
NOTE! The other dips should all remain in the "OFF"
position.
4º - Make the setting for the sensor to be recognized
by the software.
5 - To enable the intelligence function, you must set bit
2 output for this, open the slave configuration screen
by double-clicking on it.
6 - When you open the screen click on "Data and
Parameter" tab and click on bit 2 output to enable it.
Rua Tuiuti, 1237 - Tatuapé - 03081-000 - São Paulo - SP - Fone: (11) 2145-0444 - Fax: (11) 2145-0404 - e-mail: vendas@sense.com.br - www.sense.com.br
We reserve the right to modify the information contained herein without notice
12
7º - The amount of maneuvering of the valve is read in
input bits 2 and 3, as the figures below:
0 to 499 Maneuvres:
500 to 4.999 Maneuvres:
5.000 to 49.000 Maneuvres:
Above 50.000 Maneuvres:
NOTE! When doing maintenance of the valve to reset
the maneuvre counter, for this, enable output bit 1 for
at least one second.