Hlt Products Alternate Stripping Method - Nelson PLT-BC Installation Instructions Manual

Heat tracing systems standard power connection kit
Table of Contents

Advertisement

NELSON
HEAT TRACING SYSTEMS
PLT-BC
STANDARD POWER CONNECTION KIT

HLT PRODUCTS ALTERNATE STRIPPING METHOD

Lightly cut around cable outer jacket 102mm (4")
from the end. Bend cable to break outer jacket.
Lightly cut the outer jacket up the center between
the first cut mark & the cable end. Bend cable to
break outer jacket.
Remove the jacket from the heater cable.
Make a cut inside each bus wire.
P.O. BOX 726
TULSA, OK 74101
GA-1859 Rev. 6
Sheet 6 of 8
October 2006
102mm (4")
TEL 918-627-5530
Starting at the end, in the same plane as the cable,
pull each bus wire away from the core material.
Remove the exposed core material.
Remove the remaining core material off the outside
of each bus wire.
Cut 6mm (0.25") off the end of each bus wire.
Proceed to "Power Termination" on sheet 7.
FAX 918-641-7336
www.nelsonheaters.com
INSTALLATION
INSTRUCTIONS