Configuring Communication Parameters - General Measure GM8802F-2 User Manual

Field mounting transmitter
Table of Contents

Advertisement

5.1.2 Configuring parameters
After that, user can define parameters, such as baud rate, data format, communication
protocols and so on;when finished, user need dial dip switch D6 to 0(normal) and restart
power, so GM8802F-2 begin to communicate data with host computer by update parameters.
Define parameters as following fixed protocol:
Data format:7bits,1 bit stop,Even(7-E-1)
Baud rate:38400
Code:ASCII
Command:
STX
Address U
Response:
STX
Address U
Here:
STX
—— 1bit,start character 02H
Address —— 2bit,range from 01~16(30H 31H~31H 36H)
U
—— 1bit,55H
S
—— 1 bit,53H
E
—— 1 bit,45H
T
—— 1 bit,54H
DATA1 —— 1 bit,baud rate:30H:9600;31H:19200H;32H:38400;33H:57600
DATA2 —— 1 bit,communication mode:30H:MODBUS RTU;31H:MODBUS ASCI;
32H:GM-SP1
DATA3 —— 1 bit,data format
Data format table:
Communication mode
MODBUS-RTU
GM8802-F2110101
Please dial dip switch D6 from 0(normal)to 1(defining)
to configure parameters as left drawing.
Note:User need restart power after dip switch D6 changed.
S
E
T
DATA1
S
E
T
DATA3
30H
31H
32H
33H
GM8802F-2 Field Mounting Transmitter
DATA2
DATA3 DATA4 CRC
O
CR
K
CRC
CR
Data format
8-E-1
8-O-1
8-N-1
8-N-2
LF
LF
11