Instruction Sheet 3A1519RevA
IEC 61643-11 Class II, two-pole SPDs for
TN and TT 230/400V IEC applications
BSPM2275TN(R) and BSPH2275TT(R)
Hazardous Voltage
Will cause severe injury or death
Working on or near energized circuits
poses a serious risk of electrical shock.
De-energize all circuits before installing
or servicing this equipment and follow
all prescribed safety procedures
Conductors
Mounting
Torque 4 N•m
35mm
DIN-Rail
Indoor use only
90mm L x 36mm W x 73mm H
System installation
Class II IEC 61643-11...
Type 2
EN 61643-11...
There is no distance required
from the SPD to any earthed
conductive surface.
Module replacement
Effective December 2015
Supersedes December 2010
Visual indication status
System type
Voltage U
Green =
Good
Voltage U
Red =
f
N
Replace
I
fi
Max. fuse
I
SCCR
I
max
Operating environment
I
PE
Remote contact signaling
(modules installed)
Types:
Replacement
modules
Green
Green =
Ports
Good
IP rating
L x W x H
Wiring
Red
Red =
TN (-C) -S connection
Replace
Testing contact signaling
(modules removed)
Green
Remove/test
Remote OK
Remote contact signaling
TN
TT
L-N
[L N]
Tol: 0V...U
230/400V
230/400V
N
C
[N PE]
275V~
275V~
C
275V~
50/60Hz
—
125A gG
50kA
rms
40kA
-40°C to +80°C, 5%-95% RH
<0.15mA
<5µA
W/O remote
BSPM2275TN
BSPH2275TT
[L N]
W/ remote
BSPM2275TNR
BSPH2275TTR
[L PE]
—
BPM275IEC
[N PE]
BPM275IEC
—
BPM275IEC
—
1
IP20 built-in
90mm x 36mm x 73mm
TT connection
S
2
* *
S
3
S
3
* Module BPM275IEC
* Module BPM275IEC
** Module BPSNPEIEC
BUSSMANN
SERIES
Fusing
N-PE
255V~
100A
rms
—
Fusing and minimum
conductors
F1 A gG S
/mm
2
S
/mm
2
3
25
4
6
—
35
4
6
40
4
6
50
6
6
BPSNPEIEC
63
10
10
80
10
10
100
16
16
125
16
16
>125
16
16
S
2
* **
Warranty
See document No. 3A1502 at
www.cooperbussmann.com/surge
for limited warranty details.
2
F2 A gG
—
—
—
—
—
—
—
—
125
YEAR
WARRANTY