Download Print this page

Eaton BSPM2275TN Instruction Sheet

Bussmann series

Advertisement

Quick Links

Instruction Sheet 3A1519RevA
IEC 61643-11 Class II, two-pole SPDs for
TN and TT 230/400V IEC applications
BSPM2275TN(R) and BSPH2275TT(R)
Hazardous Voltage
Will cause severe injury or death
Working on or near energized circuits
poses a serious risk of electrical shock.
De-energize all circuits before installing
or servicing this equipment and follow
all prescribed safety procedures
Conductors
Mounting
Torque 4 N•m
35mm
DIN-Rail
Indoor use only
90mm L x 36mm W x 73mm H
System installation
Class II IEC 61643-11...
Type 2
EN 61643-11...
There is no distance required
from the SPD to any earthed
conductive surface.
Module replacement
Effective December 2015
Supersedes December 2010
Visual indication status
System type
Voltage U
Green =
Good
Voltage U
Red =
f
N
Replace
I
fi
Max. fuse
I
SCCR
I
max
Operating environment
I
PE
Remote contact signaling
(modules installed)
Types:
Replacement
modules
Green
Green =
Ports
Good
IP rating
L x W x H
Wiring
Red
Red =
TN (-C) -S connection
Replace
Testing contact signaling
(modules removed)
Green
Remove/test
Remote OK
Remote contact signaling
TN
TT
L-N
[L  N]
Tol: 0V...U
230/400V
230/400V
N
C
[N  PE]
275V~
275V~
C
275V~
50/60Hz
125A gG
50kA
rms
40kA
-40°C to +80°C, 5%-95% RH
<0.15mA
<5µA
W/O remote
BSPM2275TN
BSPH2275TT
[L  N]
W/ remote
BSPM2275TNR
BSPH2275TTR
[L  PE]
BPM275IEC
[N  PE]
BPM275IEC
BPM275IEC
1
IP20 built-in
90mm x 36mm x 73mm
TT connection
S
2
* *
S
3
S
3
* Module BPM275IEC
* Module BPM275IEC
** Module BPSNPEIEC
BUSSMANN
SERIES
Fusing
N-PE
255V~
100A
rms
Fusing and minimum
conductors
F1 A gG S
/mm
2
S
/mm
2
3
25
4
6
35
4
6
40
4
6
50
6
6
BPSNPEIEC
63
10
10
80
10
10
100
16
16
125
16
16
>125
16
16
S
2
* **
Warranty
See document No. 3A1502 at
www.cooperbussmann.com/surge
for limited warranty details.
2
F2 A gG
125
YEAR
WARRANTY

Advertisement

loading

Summary of Contents for Eaton BSPM2275TN

  • Page 1 Supersedes December 2010 IEC 61643-11 Class II, two-pole SPDs for Visual indication status Fusing System type TN and TT 230/400V IEC applications N-PE BSPM2275TN(R) and BSPH2275TT(R) [L  N] Voltage U Tol: 0V...U 230/400V 230/400V Green = [N  PE]...
  • Page 2 © 2015 Eaton Eaton and Bussmann are valuable 1000 Eaton Boulevard 114 Old State Road All Rights Reserved trademarks of Eaton in the U.S. and other Cleveland, OH 44122 Ellisville, MO 63021 Printed in Germany countries. You are not permitted to use Eaton.com...

This manual is also suitable for:

Bspm2275tnrBsph2275ttrBsph2275tt