Novatek-electro RS-485 Operating Manual page 13

Interface controller
Table of Contents

Advertisement

Max. number of clients of
MODBUS TCP
Max. load of
MODBUS TCP, query/s
Max. load of RS-485, %
Max. load of GSM, kB/s
Current IP-address of
Ethernet
Current MAC-address of
Ethernet
Unused parameter
Time to connect to the
data collection server
Number of programmed
restarts
Number of critical errors
Total operation time, min
Current time
Year of countdown
Time zone, min
Temperature, °C
Power voltage, mV
Time before connection to
remote server Modbus
TCP
Interface of connection to
remote server of Modbus
TCP
DST increment, min
Unused parameter
IP-address of client 1**
Port of client 1**
IP-address of client 2**
Port of client 2**
IP-address of client 3**
Port of client 3**
IP-address of client 4**
Port of client 4**
Unused parameter
Year (current time)
Month (current time)
Day of the month (current
time)
Hour (current time)
Minute (current time)
Second (current time)
Day of week (current time)
Month (winter time)
Day of the month (winter
time)
Hour (winter time)
Unused parameter
Time of day, s
Time of sunrise, s
Table 5.7 Continued
Parameter
NOVATEK-ELECTRO
Maximal number of simultaneously connected clients via Modbus
TCP - from the moment of start up
Maximal number of queries received per second from the clients via
Modbus TCP - from the moment of start up
Maximal load of RS-485 for 5 minutes - from the moment of start up
Maximal load of GPRS - from the moment of start up
IP-address, by which EM-481 device is accessible in Ethernet
network*
MAC-address, by which EM-481 is detected in Ethernet network
The parameter is reserved for compatibility and is equal to 0
0 - connection to the data collection server is set;
1 - connection to the data collection server is performed;
2 - 65534: the number of seconds before reconnecting;
65535: connection to the server is not used.
Number of restarts in accordance to the user setting - for total
operational time
Number of noted errors (failures) causing the restart of the device - for
total operational time
The number of minutes of operating time - for the total operational
time
Number of seconds since 1st of January of specified year (see reg. 172)
st
Year, since 1
of January which is taken for time counting
Time zone, for the time count, number of minutes with sign as to
UTC+00
Temperature inside EM-481
Bus voltage of 12 V
0 - connection to the remote server is set;
1 - connecting to the remote server;
2 - 65534: the number of seconds before reconnecting;
65535: Connection to the Modbus TCP server is not used.
0 - the connection is not set;
1 - Ethernet connection is set;
2 - GPRS connection is set.
Effective day saving time increment
The parameter is reserved for compatibility and is equal to 0
IP-address of client, 0.0.0.0 – not connected
Port of client, 0 – not connected
IP-address of client, 0.0.0.0 – not connected
Port of client, 0 – not connected
IP-address of client, 0.0.0.0 – not connected
Port of client, 0 – not connected
IP-address of client, 0.0.0.0 – not connected
Port of client, 0 – not connected
The parameter is reserved for compatibility and is equal to 0
Current year
Current month
Current day of the month
Current hour
Current minute
Current second
Current day of week (1 - Monday)
Current month, excluding summer time
Current day of the month, excluding summer time
Current hour, excluding summer time
The parameter is reserved for compatibility and is equal to 0
Number of seconds from midnight of the current day
0–86399: Number of seconds from midnight to sunrise;
86400: Sunrise is not observed on this day
13
-
-
Description
136
137
138
139
140 – 143
144 – 149
150 – 164
165
166
167
168 – 169
170 – 171
172
173
174
175
176
177
178
179
180 – 183
184
185 – 188
189
190 – 193
194
195 – 198
199
200 – 209
210
211
212
213
214
215
216
217
218
219
220 – 229
230 – 231
232 – 233
Address
EM-481