Novatek-electro MCK-108 Operating Manual

Novatek-electro MCK-108 Operating Manual

Pumping plant controller

Advertisement

Quick Links

«NOVATEK-ELECTRO» LTD
Intelligent Industrial Electronics
PUMPING PLANT
CONTROLLER
MCK-108
OPERATING MANUAL
Quality control system on the development and production complies with requirements ISO 9001:2015
Dear customer,
Company NOVATEK-ELECTRO LTD. thanks you for purchasing our products.
You will be able to use properly the product after carefully studying the Operating Manual.
Keep the Operating Manual throughout the service life of the product.
UKRAINE, Odessa
www.novatek-electro.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MCK-108 and is the answer not in the manual?

Questions and answers

Summary of Contents for Novatek-electro MCK-108

  • Page 1 Quality control system on the development and production complies with requirements ISO 9001:2015 Dear customer, Company NOVATEK-ELECTRO LTD. thanks you for purchasing our products. You will be able to use properly the product after carefully studying the Operating Manual. Keep the Operating Manual throughout the service life of the product.
  • Page 2 During operation and maintenance the regulatory document requirements must be met, namely: – Regulations for Operation of Consumer Electrical Installations; – Safety Rules for Operation of Consumer Electrical Installations; – Occupational Safety when in Operation of Electrical Installations; MCK-108 NOVATEK-ELECTRO...
  • Page 3: Terms And Abbreviations

    Filling mode - In this mode, MCK-108 controls the pump, filling the outer tank by pumping water from the well. Drainage mode is used for pumping liquid out of the well, for instance - in sewerage stations.
  • Page 4: Technical Characteristics

    (grease, oil, dust, etc.). 2 TECHNICAL CHARACTERISTICS General data for MCK-108 are specified in Table 1. The main technical characteristics of MCK-108 are specified in Table 2. The characteristics of the integrated relays output contacts are specified in Table 3. MCK-108...
  • Page 5: Intended Use

    Operating Manual. 3.1.2 General instructions ATTENTION! MCK-108 ARE NOT DESIGNED FOR LOAD COMMUTATION IN CASE OF SHORT CIRCUITS. THEREFORE THEY SHOULD BE PROTECTED BY AUTOMATIC CIRCUIT BREAKERS (FUSES) WITH TRIPPING CURRENT NOT EXCEEDING 10 A.
  • Page 6 If you increase the tightening torque, it is possible to have thread failure of the terminal block screws or the compression of the connected wire. To increase the running ability of MCK-108, it is recommended to install protection devices (fuse links or their equivalents) into the following circuits (enumerated in the order of necessity, hyphen is followed by the recommended protection device rating): 1) power supply circuits of MCK-108 L, N - 0.5 A;...
  • Page 7 3.1.6 When working in the filling mode with level sensors, turn the switch CPG – S.L. (CPG – Level Sensor) to "S.L." (Level Sensor) position and turn the switch Drn - FI (Drainage – Filling) to "FI" (Filling) position. 3.1.7 To connect the pressure sensor to MCK-108, one must connect the following items by using Figure 1 and Figure 3: –...
  • Page 8 - EL – emergency level; - UL – upper level; - LL – lower level; - Com. – common. Figure 5 – Application of MCK-108 in the filling mode with level sensors 1 - submersible pump 2 - MCK-108 3 – electrodes: - EL –...
  • Page 9 Figure 7. In the automated operation modes of MCK-108 with two pumps, the operation logic of the device is preserved, but the functional relay is used to control the electric motor of the second pump and, subsequently, does not respond to emergency conditions.
  • Page 10: Maintenance Procedure

    The LED UL blinks red sensor (UL) shall indicate the absence of liquid. At failure of the UL sensor, MCK-108 will continue operating, using the emergency level sensor as an UL sensor. 3.2.3.4 EEPROM Failure When EEPROM failure, calibration of resistance of liquid off and MCK-108 is locked, giving the following error message –...
  • Page 11: Transportation And Storage

    4 TRANSPORTATION AND STORAGE MCK-108 in the manufacturer's package must be stored in an indoor area at the temperature from minus 45 to +60 C and relative humidity not exceeding 80 %, provided there are no vapours, causing any damaging impact on the package and the materials of the device.