FireLock
®
Low-Profile Sprinkler Outlet-T
STYLE 912
•
Read and understand all instructions before attempting to install any Victaulic piping products.
•
Wear safety glasses, hardhat, and foot protection.
•
Depressurize and drain the piping system before attempting to install, remove, adjust, or maintain any Victaulic piping products.
Failure to follow these instructions could result in serious personal injury and/or property damage.
The Style 912 FireLock
®
Low-Profile Sprinkler Outlet-T is designed for direct connection of sprinkler heads and is FM Approved up to
300 psi/2068 kPa and VdS and LPCB Approved up to 16 Bar/232 psi at ambient temperatures that are typical for fire protection systems.
PRODUCT DATA
Y
V
W
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
REV_A
Nominal Size
inches/Actual mm
Diameter
+0.06/+1,5
Run x Branch FPT†
–0.00/–0,0
1
1/2
x
33.7
15.0
Z
1 1/4
1/2
x
42.4
15.0
1 1/2
1/2
x
48.3
15.0
† Style 912 Low-Profile Sprinkler Outlet-T products are designed with female threads to ISO 7-Rp 1/2
(Rp 1/2 BSPP per BS21) and can accommodate only male sprinkler threads.
FOR SPRINKLER USE ONLY. DO NOT USE AS A BRANCH OUTLET.
Hole
V
W
15/16
1.00
0.90
24.0
25.4
22.9
15/16
1.17
1.10
24.0
29.8
27.9
15/16
1.29
1.22
24.0
32.8
31.0
I-912
Approximate
Weight Each
Y
Z
lbs/kg
3.72
1.50
0.67
94.6
38.1
0.30
4.12
1.50
0.74
104.7
38.1
0.33
4.32
1.50
0.76
109.8
38.1
0.34
I-912_1
Need help?
Do you have a question about the FireLock 912 and is the answer not in the manual?
Questions and answers