Page 1
ART 22 DZR Balancing Valve Flow Data Installation Instructions This datasheet is designed as a guide and should not be regarded as wholly accurate in every detail.We reserve the right to amend the specification of any product without notice.
ART 22 Technical Data The Albion ART 22 is a fixed orifice double regulating valve used to regulate and measure the flow passing through it. Flow Coefficient The flow rate can be calculated using the Kv value and a measured signal.
Page 3
ART 22 Kv Values - DN 15L ART 22 Kvs=0.62 Kv (Flow rate in m /h @ 1 bar pressure drop) Full turn Tenths of turn 0.165 0.173 0.180 0.186 0.191 0.196 0.200 0.204 0.209 0.213 0.218 0.223 0.229 0.236 0.243...
Page 4
ART 22 Kv Values - DN 15ML ART 22 Kvs=1.1 Kv (Flow rate in m /h @ 1 bar pressure drop) Full turn Tenths of turn 0.154 0.166 0.175 0.183 0.189 0.193 0.198 0.201 0.205 0.209 0.213 0.219 0.225 0.232 0.240...
Page 5
ART 22 Kv Values - DN 15 Turns N° ART 22 Kvs=2.3 0.01 0.02 0.04 0.06 0.08 Flow rate - Q (l/s) Kv (Flow rate in m /h @ 1 bar pressure drop) Full turn Tenths of turn 0.47 0.68 0.83...
Page 6
ART 22 Kv Values - DN 20 Turns N° ART 22 Kvs=5.3 0.02 0.6 0.8 1 0.04 0.06 0.08 Flow rate - Q (l/s) Kv (Flow rate in m /h @ 1 bar pressure drop) Full turn Tenths of turn 0.54...
Page 7
ART 22 Kv Values - DN 25 Turns N° ART 22 Kvs=9.2 0.02 0.6 0.8 1 0.04 0.06 0.08 Flow rate - Q (l/s) Kv (Flow rate in m /h @ 1 bar pressure drop) Full turn Tenths of turn 0.96...
Page 8
ART 22 Kv Values - DN 32 Turns N° ART 22 Kvs=19.0 0.06 0.08 Flow rate - Q (l/s) Kv (Flow rate in m /h @ 1 bar pressure drop) Full turn Tenths of turn 1.56 1.96 2.34 2.68 3.04 3.40...
Page 9
ART 22 Kv Values - DN 40 Turns N° ART 22 Kvs=22.1 8 10 Flow rate - Q (l/s) Kv (Flow rate in m /h @ 1 bar pressure drop) Full turn Tenths of turn 3.37 4.08 4.51 5.12 5.60 6.16...
Page 10
ART 22 Kv Values - DN 50 Turns N° ART 22 Kvs=42.3 8 10 0.6 0.8 1 Flow rate - Q (l/s) Kv (Flow rate in m /h @ 1 bar pressure drop) Full turn Tenths of turn 4.39 5.65 6.72...
This fixed orifice double regulating valve is a precision manufactured product and should be handled, installed and used with care as detailed in these instructions. ART 22 balancing valves are suitable for both heating (LPHW) and cooling applications at working pressures up to 25 bar.
Page 12
ART 22 Part Name Materials Body DZR Brass Bonnet DZR Brass Stem DZR Brass ½” ¾” 1” 1¼” 1½” 2” Gasket EPDM Shutter DZR Brass Index 72.5 Entrainer Blue Nylon 6 116.5 Knob Blue Nylon 6 12.5 12.5 14.5 1/10 Turn index blue...
ART 22 Installation Valves are precision manufactured products and should not be subjected to misuse. Careless handling, allowing foreign particles to enter the valve through the end ports, lack of cleaning both valve and system before operation should be avoided. Excessive force during pipe tightening and handwheel operation should be avoided.
• The double regulating feature is now set which enables the valve to be fullyclosed for isolation and re-opened to the previously set position. It is recommended to record this set position for reference later if necessary. Maintenance The Albion Art 22 does not require any routine maintenance.
Need help?
Do you have a question about the ART 22 and is the answer not in the manual?
Questions and answers