Siemens RUGGEDCOM RS400 Installation Manual page 45

Hide thumbs Also See for RUGGEDCOM RS400:
Table of Contents

Advertisement

RUGGEDCOM RS400
Installation Guide
Test
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 60255-5
IEEE 1613 (C37.90.x) EMC Immunity Type Tests
NOTE
The RUGGEDCOM RS400 meets Class 2 requirements for an all-fiber configuration and Class 1
requirements for copper ports.
ESD
Radiated RFI
Fast Transient
Oscillatory
Dielectric Strength
HV Impulse
EMC and Environmental Type Tests
Description
Damped Oscillatory
DC Power Ports
AC Power Ports
Mains Frequency
Voltage
DC Power Ports
Ripple on DC
DC Power Ports
Power Supply
Dielectric Strength
DC Power Ports
AC Power Ports
H.V. Impulse
DC Power Ports
AC Power Ports
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
100% for 5 periods, 100% for 50 periods
Signal Ports
2.5 kV common, 1 kV differential mode at 1 MHz
2.5 kV common, 1 kV differential mode at 1 MHz
2.5 kV common, 1 kV differential mode at 1 MHz
Signal Ports
30 V Continuous, 300 V for 1 s
30 V Continuous, 300 V for 1 s
Signal Ports
2 kVac (Fail-Safe Relay Output)
Signal Ports
1 kV Common and Differential Mode at 1 MHz
1 kV Common and Differential Mode at 1 MHz
Test Levels
10%
1.5 kVDC
2 kVAC
5 kV (Fail-Safe Relay output)
5 kV
5 kV
Test Levels
±8 kV
±15 kV
35 V/m
±4 kV at 2.5 kHz
±4 kV
±4 kV
±4 kV
2.5 kV Common Mode at 1 MHz
2 kVAC
1.5 kVDC
2 kVAC
5 kV (Failsafe Relay)
Chapter 6
Certification
Severity
Levels
2
3
3
3
4
4
3
35