Modbus RTU Connection Details 
 
Modbus RTU protocol selection and addressing is done using the PC tool OCI Configuration 
Utility (see next section).   
 
Supported addresses: 1‐247 
Supported baud rates: 2400, 4800, 9600, 19200, 38400, 57600, and 115200 
Supported data bits: 8 
Supported parity and stop bits: none (1 or 2 stop bits), odd (1 stop bit), and even (1 stop bit) 
Supported function codes: 3 (read holding registers), 4 (read input registers), 6 (write single 
holding register), and 16 (write multiple holding registers) 
Maximum read length: 125 (if beginning and ending registers are valid addresses) 
 
 
 
  
 