LG RCAW Operation & Maintenance Manual page 67

Chiller air-cooled screw compact (50hz)
Table of Contents

Advertisement

Maintenance
Maintenance Schedule
Check Point
1. Cycle Status
2. Electric part
3. Safety switches
4. Water Loop System
5. Condenser cleanness
6. Cooling tower
cleanness
7. Refrigerant
system leakage
8. Oil filter
9. Dryer filter
10. Oil Level
11. Oil color
12. Compressor
insulation
13. Temperature
sensor
14. Compressor
bearing
Every
Daily
Monthly
2 months
10h
500h
1000h
Check
Check
-
Check
-
Check
-
-
-
-
-
-
Check
-
-
-
Check
-
-
Check
Check
-
Check
-
-
-
-
-
Check
-
-
-
-
Every
Every
3 months
6 months
1500h
2500h
Monthly check
Monthly check
Clean
Check every 6 months
Check every 6 months. When the operating pressure
Check
of the cooler is out of the range, clean the unit.
Check
Clean
Monthly check
Replace
Check every 6 months. Clean if necessary.
-
Replace
Annual check
-
-
Replace
-
Check
Check every 6 months
-
-
Table 24
Operation & Maintenance Manual 67
Every
Every
Every
1 year
2 years
3 years
5000h
10000h
15000h
Annual clean
Annual replacement
-
Annual check
-
-
Check
Service
Every
6 years
30000h
-
Check or
replace

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents