LG RCAW Operation & Maintenance Manual page 29

Chiller air-cooled screw compact (50hz)
Table of Contents

Advertisement

The MODBUS address map of registers is shown in the below table.
NO
MODBUS Address
46101
1
46102
2
46103
3
4
46104
5
46105
46106
6
7
46108
8
46109
46110
9
10
46115
11
06111
Meaning
Chilled Water Out Temp
Chilled Water In Temp
Ref Cond Out Temp
Ambient Temp
Comp Exhaust Temp
Comp Capacity Rate
Running Hours
Running Status
Control Status
-
-
Indicating Unit
Actual Value x 10 [°C]
Actual Value x 10 [°C]
Actual Value x 10 [°C]
Actual Value x 10 [°C]
Actual Value x 10 [°C]
%
Hour
65: Starting, 66: Delaying, 67: Running
68: Shut -downing, 69: Stop
BIT0: Fault, BIT1: Comp Main MC
BIT2: Comp
MC, BIT3: Comp Y MC
Actual Value(5°C ~ 12°C) x 10 [°C]
0: Stop, 1: Start
Table 8
Operation & Maintenance Manual 29
Controls
Write
-
-
-
-
-
-
-
-
-
YES
YES