Maintenance/Removal; Accessories - Honeywell BK-G1.6A Operating Instructions Manual

Diaphragm gas meters
Table of Contents

Advertisement

WARNING
The grid operator is responsible for the safe
remote shut-down and restart of the diaphragm
gas meter.
The integrated valve does not assume the func-
tions of a safety shut-off valve.
▷ Should the diaphragm gas meter BK be ordered
with a valve, but without control electronics to
be complemented by a third party, the technical
data of the control interface is to be requested
from Elster GmbH and observed.
▷ The manufacturer of the control electronics is
responsible for creating the conditions required
for safe operation of the valve. Instructions on
commissioning and operation are to be taken
from the operating instructions for the control
electronics.
... with valve variant Ve
▷ Notes on the function can be found in the operat-
ing instructions of the electronic index. Technical
data, see page 9 (Technical data).
... with valve variant Vs (Smart Valve)
WARNING
Depending on national regulations, a limited
and technically safe gas flow rate in the cus-
tomer's open consumer piping is allowed, see
page 9 (Technical data).
Assessment of the non-critical gas flow rate with
regard to amount and duration, which occurs
when the valve is released, is to be carried out
by the grid operator.
The minimum operating pressure on the inlet
must not be undershot, see page 9 (Techni-
cal data). Otherwise, when the valve is released
and if the customer's consumer piping is open
at the same time, the valve may be completely
opened.
"Smart Valve" valve function
▷ The "Smart Valve" is switched remotely by the data
management system. The valve first switches to
the "Released" position. From the "Released" posi-
tion, the valve automatically switches to the "Open"
position, if the downstream installation is tight.
Released
▷ The "Smart Valve" opens an internal bypass and
releases a minimum gas flow into the customer's
closed consumer piping. Pressure equalization
takes place between the inlet and outlet side
of the valve.
Open
▷ Following pressure equalization, the valve auto-
matically opens by spring force and fully releases
the gas supply. If consumers of the customer are
open, pressure equalization cannot occur and
the valve remains in the "Released" position and
continues to release only the minimum gas flow
rate of the bypass.
Closed
▷ The valve and the bypass are closed in the event
of remote shut-down.
▷ All valve positions are kept when de-energized.

Maintenance/Removal

Gas meters BK-G1.6 to 25 from Elster are mainte-
nance-free (constraints for BK-G...E... and BK-G...B).
▷ When used for custody transfer measurements,
recalibration must be carried out in accordance
with national directives.
▷ If the screw unions are loosened for maintenance
work or retesting, replace the seals.
▷ After the gas meter has been removed, immedi-
ately close the connectors with protective caps
in order to prevent ingress of dirt particles.
▷ For meters with electronic indexes (BK-G...E...
and BK-G...B), it may be necessary to change
the battery, see "Operating instructions for op-
erators and installers" for the corresponding
electronic index.
WARNING
A certain amount of gas may remain in the gas
meter. Taking into consideration the risk of explo-
sion, it is important to adopt safety measures, e.g.:
Following removal of the gas meter, purge it
thoroughly with inert gas.
For transporting the gas meter with gas residue,
use a vehicle with an open or a ventilated load-
ing area.
The indexes must not be opened in an explo-
sion-hazard area even for maintenance and
repair. Opening of the service cover on the
electronic index, e.g. to change the battery,
is permitted – see "Operating instructions for
operators and installers" for the corresponding
electronic index.
Meters which are installed in a potentially ex-
plosive atmosphere may only be cleaned using
a damp cloth to avoid static electricity charge.

Accessories

We recommend using Elster GmbH accessories only.
Pulse transmitters of the IN-Z6x series
▷ Also for devices which are marked with
IN-Z6 (Part No. 32319615)
Retrofit kit with connection cable –
Order No. 72910109
Retrofit kit without connection cable –
Order No. 72910114
IN-Z6 (Part No. 32319616)
Shipping unit – Order No. 32447303
IN-Z6 (Part No. 32319617)
Retrofit kit – Order No. 72910110
Retrofit kit with cable socket – Order No. 72910112
GB-8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents